Cabling and connections 43(86), Control terminal signals – Nx Networks NX series User Manual

Page 43

Advertising
background image

Cabling and connections

43(86)

6

6.2.2

Control terminal signals

Terminal

Signal

Technical information

1

+10 Vref

Reference voltage

Maximum current 10 mA

2

AI1+

Analogue input,
voltage or current

Selection V or mA with jumper block X1

(see page 45):

Default: 0– +10V (Ri = 200 k

)

(-10V…..+10V Joy-stick control, selected with a jumper)
0– 20mA (Ri = 250

)

3

GND/AI1–

Analogue input common

Differential input if not connected to ground;
Allows

±

20V differential mode voltage to GND

4

AI2+

Analogue input,
voltage or current

Selection V or mA with jumper block X2

(see page 45):

Default: 0– 20mA (Ri = 250

)

0– +10V (Ri = 200 k

)

(-10V…..+10V Joy-stick control, selected with a jumper)

5

GND/AI2–

Analogue input common

Differential input if not connected to ground;
Allows

±

20V differential mode voltage to GND

6

24 Vout
(bidirectional)

24V auxiliary voltage

±

15%, maximum current 250mA (all boards total);150mA

(from single board); Can also be used as external power
backup for the control unit (and fieldbus)

7

GND

I/O ground

Ground for reference and controls

8

DIN1

Digital input 1

9

DIN2

Digital input 2

10

DIN3

Digital input 3

R

i

= min. 5k

11

CMA

Digital input common A for
DIN1, DIN2 and DIN3.

Must be connected to GND or 24V of I/O terminal or
to external 24V or GND

Selection with jumper block X3

(see page 45):

12

24 Vout
(bidirectional)

24V auxiliary voltage

Same as terminal #6

13

GND

I/O ground

Same as terminal #7

14

DIB4

Digital input 4

15

DIB5

Digital input 5

16

DIB6

Digital input 6

R

i

= min. 5k

17

CMB

Digital input common B for
DIB4, DIB5 and DIB6

Must be connected to GND or 24V of I/O terminal or
to external 24V or GND

Selection with jumper block X3

(see page 45):

18

AO1+

Analogue signal (+output)

19

AO1–

Analogue output common

Output signal range:
Current 0(4)–20mA, R

L

max 500

or

Voltage 0—10V, R

L

>1k

Selection with jumper block X6

(see page 45):

20

DO1

Open collector output

Maximum U

in

= 48VDC

Maximum current = 50 mA

NXOPTA3

21

RO1/1

22

RO1/2

23

RO1/3

Relay output 1

Maximum switching voltage 250VAC, 125VDC
Maximum switching current 8A/24VDC,

0.4A/250VDC

Min. switching load

5V/10mA

25
26

RO2/1
RO2/2

Relay output 2

Maximum switching voltage 250VAC, 125VDC
Maximum switching current 8A/24VDC, 0.4A/250VDC
Min. switching load

5V/10mA

28
29

TI1/1
TI1/2

Thermistor input 1

Basic galvanic isolation
Double isolation when connected to thermistor

Table 6-5. Control I/O terminal signals