Low voltage terminal strip – Nortec Industries GS Series User Manual

Page 18

Advertising
background image

- 14 -

WA R N I N G : F a i l u r e t o w i r e t h e c o n t r o l l e r i n a c c o r d a n c e w i t h t h e w i r i n g d i a g r a m t h a t w a s s u p p l i e d
w i t h t h e u n i t c o u l d p e r m a n e n t l y d a m a g e t h e G S T C / G S P b o a r d . S u c h e r r o r s w i l l v o i d t h e u n i t w a r r a n t y.

GS SERIES

EXTERNAL CONTROLS WIRING CONNECTIONS

LOW VOLTAGE TERMINAL STRIP

NOTE: This is a

wiring diagram only. For specific wiring instructions, it is necessary to refer

to the wiring diagram which is supplied with each unit.

generic

1

2

3 4

6

5

7

8

9 10

12

11

EXTERNAL

INTERNAL

EXTERNAL

INTERNAL

Security Loop

Modulation

Input

Signal

“A"

Modulation

Input

Signal

“B”

10

Vdc

output

Full

T

ank

Blow

Down

(FTBD)

enable

(24

V

ac)

Safety

Interrupt

(24

V

ac)

NOTE: If no On/Off Control is used then a field jumper
must be connected across terminals 1 and 2 in order
for the humidifier to operate.

14

18

15 16 17

13

COM

COM

COM

COM

N.O.

N.O.

N.O.

N.O.

N.C.

Humidifier

“ON”

Humidifier

“ACTIVE”

Humidifier

“SER

VICE”

Humidifier

“F

AUL

T”

Low Voltage Terminal Strip

1 & 2: Wire all on/off controls and safeties between these two terminals. If not used, jumper 1 & 2 for the

unit to operate.

4: Modulating input to humidifier “A”.

5: Modulating input to humidifier “B”.

6: 10 Vdc output.

8: When 24 Vac input received, the unit will initialize a full tank blowdown.

9: Safety interrupt (24 Vac).

10 & 11: Remote indication connection for humidifier “on” status indication.

12 & 13: Remote indication connection for humidifier “active” status.

14 & 15: Remote indication connection for service required indication.

16 & 17 & 18: Remote indication connection for fault indication.

+

+