FAULT LIST

GSTC fault

displayed

GSP fault code

displayed

Description of fault

Troubleshooting

FAULT

NO BURNERS

AVAILIBLE

NBF

Once the GS controller detects an ignition

module fail, it will index to the next available

ignition module. If all ignition modules have

failed or there are none available (in the case of

a 100 unit) this fault will be generated

-Check red LED’s on all modules for
flashing fault code
-Ensure there is gas supply to the
humidifier
-Ensure that the burners have not been
disabled in the software
-Consult factory

FAULT

AIR PROVING

SWITCH X OPEN

WITH

BLOWERS ACTIVE

AOF-X

On startup after 3 tries if the AP switch does

not close within the proving period, this fault

will be generated

-Check that blue hoses on the Air
Proving switch have not come loose.
-Check that wires on the Air Proving
switch are on the N/O contacts
-If available, swap Air Proving switch
with another and see if the fault follows
the air proving switch, if so, replace
switch
-Consult factory

FAULT

AIR PROVING

SWITCH X

CLOSED WITH

BLOWERS
INACTIVE

ACF-X

On initial startup if any of the A/P switches are

closed this fault will be generated.

-Ensure that wiring on the air proving
switch is on the N/O contacts
-Ensure that there is no continuity
between the switch with the wires off,
if so replace switch
-Ensure that there is not a strong
positive pressure in the room holding
the switch closed
-Consult factory

FAULT

BLOWER X

RPM HIGH

BHF-X

If the blower RPM is above the RPM tolerance

for more than 10 seconds, this fault is

generated and the humidifier stops.

-Check wiring to lead blower and
ensure a good connection.
-Check lead blower for any restrictions
by testing it in the diagnostics screen.
-Consult factory

FAULT

BLOWER X

RPM LOW

BLF-X

If the blower RPM is below the RPM tolerance

for more than 10 seconds, this fault is

generated and the humidifier stops

-Check wiring to blower X and ensure
a good connection.
-Check blower X for any restrictions by
testing it in the diagnostics screen.
-Consult factory

FAULT

BLOWER X

NOT OPERATIONAL

BNF-X

On startup, if the blower RPM does not exceed

500 RPM within 5 seconds or if during

operation, the RPM drops below 500 RPM for

more than 5 seconds this fault is generated

-Ensure there is power to the blower
and that all wires are making a proper
connection.
-Consult factory

FAULT

ILLEGAL GAS

VALVE

BURNER X

GVF-X

If the controller detects that a gas valve has

activated at a time it should not this fault is

Generated.

-Ensure that the ignition module is not
miswired or that the module is not
faulty by swapping it with a known
good one. If the problem follows the
ignition module, replace the module
-Consult factory

- 60 -