Plumbing 15, Fill wa ter supply line 15, Drain line 15 – Nortec Industries GS Series User Manual

Page 61: Aux drain port 16

Advertising
background image

FTBD Hour

Works in conjunction with FTBD hours.

Here the user sets the time of day (24 hour format) when they want the FTBD to execute. The time can be set to

trigger the cycle during off hours, when the humidity requirements are minimal.

The time is adjusted in one-hour increments.

Blowdown Rate

This parameter adjusts the frequency of blowdown cycles.

Depending on water quality, the blowdown rate can be adjusted from 5% to 50%. The percentage is based on the

steam production rate i.e. a 10% BD rate will drain 10 kg. of water for every 100 kg. of steam produced.

The higher the mineral content of the water the higher the BD rate should be set.

Float Check

This parameter sets the time of day the controller will force a float check.

Float checks are important to ensure the water level detection system is operating correctly. The float check also

tests the fill and drain system and will report any problems detected.

To set the time of day, highlight the selection then enter the user code (0335). Press enter. Use the UP/DOWN

arrows to adjust the hours (24 hour format). Pressing enter saves the setting and indexes the display to minutes. Use
the UP/DOWN arrows to adjust the minutes. Pressing enter saves the setting and returns the user to the previous
menu.

BLOWDOWN RATE
CHANGE VALUE XX%
STEAM OUTPUT

DATE/TIME/UNITS

FTBD HOURS

XXX

FTBD HOUR

XX

BLOWDOWN RATE

XX%

FLOAT CHECK

HH:MM

FILL CORRCTN

XX%

DRAIN CORRCTN

XX%

DRAIN COOL:

ON

LANGUAGE CONTROLS

WATER MANAGEMENT

CONTROL TYPE
CAPACITY LIMIT

CALIBRATE

0335

FLOAT CHECK
CHANGE VALUE HH:MM

DATE/TIME/UNITS

FTBD HOURS

XXX

FTBD HOUR

XX

BLOWDOWN RATE

XX%

FLOAT CHECK

HH:MM

FILL CORRCTN

XX%

DRAIN CORRCTN

XX%

DRAIN COOL:

ON

LANGUAGE CONTROLS

WATER MANAGEMENT

CONTROL TYPE
CAPACITY LIMIT

CALIBRATE

0335

DRAIN COOL:
ON
OFF
SMART

DATE/TIME/UNITS

FTBD HOURS

XXX

FTBD HOUR

XX

BLOWDOWN RATE

XX%

FLOAT CHECK

HH:MM

FILL CORRCTN

XX%

DRAIN CORRCTN

XX%

DRAIN COOL:

ON

LANGUAGE CONTROLS

WATER MANAGEMENT

CONTROL TYPE
CAPACITY LIMIT

CALIBRATE

0335

- 57-

Advertising