3 day drain, Keep warm, Maintenance (gsp) – Nortec Industries GS Series User Manual

Page 43: Analog channel 1, Analog channel 2

Advertising
background image

3 DAY DRAIN

3 DAY DRAIN FUNCTION

SW3/7

Function Disabled

OFF

Function Enabled (Factory set)

ON

KEEP WARM

3 DAY DRAIN FUNCTION

SW5/7

Function Enabled

ON

Function Disabled (Factory set) - 3 day drain

OFF

MAINTENANCE (GSP)

MAINTENANCE INTERVAL (GSP)

SW3/8

500 hour (Factory set)

OFF

1000 hour

ON

ANALOG CHANNEL 1

Input Range

SW1/1

SW4/1

SW 4/2

0-10V input

OFF

OFF

OFF

0-5V input

OFF

ON

OFF

2-10V input

OFF

OFF

ON

1-5V input

OFF

ON

ON

0-20mA input

ON

OFF

OFF

0-10mA input

ON

ON

OFF

4-20mA input

ON

OFF

ON

2-10mA input

ON

ON

ON

ANALOG CHANNEL 2

Input Range

SW1/2

SW4/3

SW 4/4

0-10V input

OFF

OFF

OFF

0-5V input

OFF

ON

OFF

2-10V input

OFF

OFF

ON

1-5V input

OFF

ON

ON

0-20mA input

ON

OFF

OFF

0-10mA input

ON

ON

OFF

4-20mA input

ON

OFF

ON

2-10mA input

ON

ON

ON

- 39 -