Nortec Industries GS Series User Manual

Page 30

Advertising
background image

- 26 -

SUPPLY WATER LINE

£

Nortec supplied adapter installed on fill valve (½”NPT)

£

Manual shut off valve and union installed

£

Verified pressure (30 – 80 psig)

£

Water source of 10 l/min (2.6 gpm)

£

Leak tested

£

½” dia. At max 4ft of the unit

DRAIN LINES

£

Air gap located within 3ft of the unit

£

Minimum drain line size of 1” in dia

.

£

Downward slope

£

Tundish (funnel) installed to provide air gap

£

Temperature rating of piping

£

Hose connections tightened

£

Auxiliary drain piped with shut off valve to tundish

WATER QUALITY

-

Well water

£

-

City water

£

-

Softened water

£

-

RO/DI water

£

Conductivity:

_______

mhmos Hardness:

______

_GPG

Silica

____

ppm Chlorides:

_______

ppm

pH:

_______

NOTE: Failure due to chloride corrosion is not covred under Nortec’s standard warranty. Consult
factory for more information.

ELECTRICAL INSTALLATION

£

Comply with local regulations

£

Proper supply voltage (must match rating plate) and breaker size

£

Electrical disconnect switch close to humidifier

£

Cables properly affixed

£

Low voltage wiring & control signal(s) wired to correct terminals

£

Humidifier configured for correct control signal(s)

TYPE OF CONTROLS INSTALLED/ LOCATION/ WIRING/ SETTING

£

High Limit

______________________________

£

Air Proving

_____________________________

£

Modulation Control

________________________

£

On/Off Control

___________________________

£

Controls by Nortec

________________________

£

Controls by Others

________________________