Language Controls

This field allows the user to select the menu language of choice (English, French, German)

Here the user can select the language of choice for the menu displays. To set the language, highlight the

selection then enter the user code (0335). Press enter. Use the UP/DOWN arrows to select the choice (English,
French, German). Pressing enter saves the setting and returns the user to the previous menu.

NOTE: ONLY ENGLISH AVAILABLE AS OF 05/03

Water Management

This section allows the user to set time based parameters and adjust water control parameters.

FTBD Hours

This section allows the user to set the frequency of full tank blowdowns (FTBD). FTBD’s drains and re-fills the

entire contents of the humidifier after a preset accumulated operating time. Run time is measured in steam hours
(weighted run time hours), and can be adjusted from 0 hours (feature off) to 400 hours in 25 hour increments.

Once the FTBD time has expired, the controller will wait until the FTBD hour to initiate the cycle. This prevents

random drains at times when they would be inconvenient.

SELECT LANGUAGE
ENGLISH
FRENCH
GERMAN

SELECT LANGUAGE
ENGLISH
FRENCH
GERMAN

DATE/TIME/UNITS
LANGUAGE CONTROLS

WATER MANAGEMENT

CONTROL TYPE
CAPACITY LIMIT

CALIBRATE

FTBD HOURS

CHANGE HOURS? XXX

DATE/TIME/UNITS

FTBD HOURS

XXX

FTBD HOUR

XX

BLOWDOWN RATE

XX%

FLOAT CHECK

HH:MM

FILL CORRCTN

XX%

DRAIN CORRCTN

XX%

DRAIN COOL:

SMART

LANGUAGE CONTROLS

WATER MANAGEMENT

CONTROL TYPE
CAPACITY LIMIT

CALIBRATE

0335

FTBD HOUR

CHANGE HOUR? XXX

DATE/TIME/UNITS

FTBD HOURS

XXX

FTBD HOUR

XX

BLOWDOWN RATE

XX%

FLOAT CHECK

HH:MM

FILL CORRCTN

XX%

DRAIN CORRCTN

XX%

DRAIN COOL:

ON

LANGUAGE CONTROLS

WATER MANAGEMENT

CONTROL TYPE
CAPACITY LIMIT

CALIBRATE

0335