WARNING LIST

GSTC Warning

displayed

GSP warning

displayed

Description of warning:

Troubleshooting

WARNING

IGNITION MODULE X

FAIL

IMW-X

Once the controller activates an ignition module, it will
allow 4 minutes for the gas valve to activate. After the trial
period, if the gas valve has not activated, a fault will be
generated. The module will be locked out and the next
burner will be indexed.

SEE FAULT LIST

WARNING

AIR PROVING SWITCH X

OPEN WITH

BLOWERS ACTIVE

APW-X

Should the air proving switch open while the unit is
operating this warning is generated. The controller shuts
down and retries. There are no limits to the amount of times
this warning is generated.

SEE FAULT LIST

WARNING

AIR PROVING SWITCH X

OPEN WITH

BLOWERS ACTIVE

AOW-X

On startup if the AP switch does not close within the proving
period. After 3 tries, a fault will be generated.

SEE FAULT LIST

WARNING

BLOWER X

RPM HIGH

BHW-X

If a blower RPM is above the RPM tolerance limit this
warning is generated. If it is above the RPM tolerance limit
for more than 10 seconds a fault will be generated.

SEE FAULT LIST

WARNING

BLOWER X

RPM LOW

BLW-X

If a blower RPM is below the RPM tolerance limit this
warning is generated. If it is below the RPM tolerance limit
for more than 10 seconds a fault will be generated.

SEE FAULT LIST

WARNING

MAINTENANCE TIME

HAS ELAPSED

HMW

In the user menu the user sets the maintenance time. Once

this time expires this warning is displayed. The maintenance

time is measured in weighted operational hours.

With switch 5, #4 activated, this warning will remain until

the warning is reset in the User level

SEE FAULT LIST

WARNING

Too LONG TO FILL

UNW-6

Low water level has not been reached within expected time

interval during initial fill sequence. Unit will continue filling

while warning is displayed. A Water Fill Fail fault will be

generated if the low water level is not reached after an

additional length of time.

SEE FAULT LIST

WARNING

KEEP WARM ACTIVE

SYSTEM DEMAND

ACTIVATED AT 75%

UNW-C

Keep warm feature has initiated combustion sequence at

75% output. This occurs when keep warm feature has been

activated via dip-switch settings, the system demand is

below minimum and the tank temperature sensor is

registering cold (open contacts).

-Warning message
will stop being
displayed once tank
temperature sensor
indicates water is
warm
-Keep warm feature
can be disabled using
dip-switch settings