Top or rear exit vertical termination, 90° h – Napoleon Fireplaces Castlemore GDS26N User Manual

Page 13

Advertising
background image

13

W415-0607 / A / 01.18.08

REQUIRED

VERTICAL RISE

IN FEET

V

T

HORIZONTAL VENT RUN PLUS OFFSET IN FEET

H

T

The shaded area within the lines represents acceptable
values for H

T

and V

T

.

Example 6:

V

1

= 5 ft

V

2

= 6 ft

V

3

= 10 ft

V

T

=

V

1

+

V

2

+

V

3

= 5 + 6 + 10 = 21 ft

H

1

=

8

ft

H

2

=

2.5

ft

H

R

=

H

1

+

H

2

= 8 + 2.5 = 10.5 ft

H

O

= .03 (four 90° elbows - 90°)

= .03 (90 + 90 + 90 + 90 - 90) = 8.1 ft

H

T

=

H

R

+

H

O

= 10.5 + 8.1 = 18.6 ft

H

T

+ V

T

= 18.6 + 21 = 39.6 ft

Formula 1:

H

T

< V

T

18.6 < 21

Formula 2:

H

T

+ V

T

< 40 feet

39.6 < 40

Since both formulas are met, this vent confi guration is
acceptable.

FIGURE 16

For vent confi gurations requiring more than zero 90° elbow
(top exit) or one 90° elbow (rear exit), the following formulas
apply:

Formula 1: H

T

< V

T

Formula 2: H

T

+ V

T

< 40 feet

Simple venting confi gurations

TOP OR REAR EXIT VERTICAL TERMINATION

90°

90°

90°

H

2

V

3

90°

FIGURE 17

V

1

H

1

V

2

0

5

10

15

20

40

10

20

30

3

(H

T

) < (V

T

)

See graph to determine the required vertical rise

V

T

for the

required horizontal run

H

T

.

Advertising