Typical vent installations, Special vent installations, Corner termination – Napoleon Fireplaces Castlemore GDS26N User Manual

Page 6: Periscope termination, Rear exit top exit

Advertising
background image

6

W415-0607 / A / 01.18.08

16”

MINIMUM

40 FT MAXIMUM

3 FT MINIMUM

16”

MINIMUM

40 FT MAXIMUM

3 FT MINIMUM

TYPICAL VENT INSTALLATIONS

FIGURE 2a

FIGURE 3a

* Refer to "Venting" Section

The maximum vent length for a corner installation is 20" of
horizontal run, in addition to the 45° offset. In this case zero
rise is acceptable. See FIGURE 5a. It is recommended to
maintain a 6" rise. See FIGURE 5b.

CORNER TERMINATION

FIGURE 5b

FIGURE 5a

20” MAXIMUM

6” RISE

MINIMUM

SPECIAL VENT INSTALLATIONS

Use the GD201 periscope kit to locate the air termination
above grade. The periscope must be installed so that when
fi nal grading is completed, the bottom air slot is located a
minimum of 12 inches above grade. The maximum allowable
vent length is 10 ft.

PERISCOPE TERMINATION

FIGURE 4b

FIGURE 4a

24”

MINIMUM

12”

MINIMUM

24”

MINIMUM

12”

MINIMUM

MAXIMUM 10FT VENT LENGTH

FIGURE 2b

20" MAXIMUM

29

1

/

8

" MINIMUM

PLUS RISE*

35

1

/

2

"

FIGURE 3b

24" MAXIMUM

10"

MINIMUM

45

1

/

2

" MINIMUM

PLUS RISE*

35

1

/

2

"

HORIZONTAL VENT SECTIONS: A minimum clearance
of 1" at the bottom and sides and 2" at the top of the
vent pipe in all horizontal runs to combustibles is
required. Use fi restop spacer W010-1313 and shield
W585-0240 (supplied).

REAR EXIT

TOP EXIT

VERTICAL VENT SECTIONS: A minimum of 1"
all around the vent pipe on all vertical runs to
combustibles is required

.

Use fi restop spacer W010-

1313 (supplied).