Vertical through existing chimney – Napoleon Fireplaces Castlemore GDS26N User Manual

Page 14

Advertising
background image

14

W415-0607 / A / 01.18.08

VERTICAL THROUGH EXISTING CHIMNEY

This appliance is designed to be attached to a 3" co-linear
fl exible vent system running the full length of a masonry
chimney.

The fl exible vent pipe accommodates any contours of a masonry
chimney, however, it is necessary to keep the fl exible vent pipe
as straight as possible. The inlet air collar of the termination
cap must be connected to the air intake pipe.

Use Simpson Duravent Chimney Liner Termination Kit -
923GK (Base plate and Co-Linear to Co-Axial Adaptor.
Follow manufacturers (Simpson Dura-Vent) installation
instructions.
When installing the unit to this system, Duravent vent
components must be used. You must start with a Duravent
adaptor, GDS924N, directly off the unit. The GDS924N is only
available at your Napoleon® dealer.

INSTALLATION

FIGURE 18

40 FEET

MAXIMUM

3 FEET

MINIMUM

FLEX

VENT

PIPE

EXHAUST

FLUE

PIPE

AIR

INTAKE

PIPE