Warning, 4 alarm output wiring (option) – Omega RD260A User Manual

Page 20

Advertising
background image

2 - 8

2.2.4 Alarm Output Wiring (option)

!

NOTE

The following settings are available only for the model with relay options (-A2,
-A4, -A6).

(1) Turn the power switch off.
(2) Remove the transparent cover of the optional terminals.
(3) Connect the alarm output wires to the optional terminals.
(4) Cover the terminals with the transparent cover and secure the screws.
Depending on the type (the number of outputs) of alarm relay options, the terminal
arrangement changes as shown in the following:

ALARM

!

1

2

3

4

5

6

ALARM

!

1

2

3

4

ALARM

!

1

2

NO

NC

C

NO

NC

C

NO

NC

C

NO

NC

C

NO

NC

C

NO

NC

C

NO

NC

C

NO

NC

C

NO

NC

C

NO

NC

C

NO

NC

C

NO

NC

C

-A2 option
(2 outputs)

- A4 option
(4 outputs)

-A6 option
(6 outputs)

Alarm Output Terminal Arrangements

Contact characteristics:

Output type

: Relay transfer contacts

Output capacity

: 250 V AC (50/60 Hz), 3 A

250 V DC, 0.1 A (resistive load)

Dielectric strength : 1500 V AC (50/60 Hz) for one minute between output terminals

and grounding terminals

To prevent an electric shock, ensure the main power switch is turned off before
wiring.

NOTE

To prevent an emission of electromagnetic disturbances, separate the alarm
output wires from the power supply and input wires at least 0.1 m. Over 0.5 m
is recommended.

WARNING

Advertising