Warning – Quadra-Fire SAPPHIRE-D-CSB User Manual

Page 25

Advertising
background image

25

Quadra-Fire • Sapphire • 7055-116 Rev. D • 6/11

B. Gas Pressures

If the pressure is not suffi cient, ensure:

1) The piping used is large enough.

2) The supply regulator is adequately adjusted.

3) That the total gas load for the residence does not exceed

the amount supplied.

The regulator that attaches directly to the residence inlet or
to the propane tank is the supply regulator. It should supply
gas at the suggested input pressure listed above. Contact the
local gas supplier if the regulator is at an improper pressure.

Pressure requirements for appliance are shown in the table
below.

Proper input pressures required for optimum appliance per-
formance, gas line sizing requirements need to be followed
from NFPA51.

NOTE: A listed (and Commonwealth of Massachusetts
approved) 1/2 inch (13mm) T-handle manual shut-off valve and
fl exible gas connector are connected to the 1/2 inch (13mm)
control valve inlet.
• If substituting for these components, please consult local

codes for compliance.

NOTE: The gap between the supply piping and gas access
hole may be plugged with non-combustible insulation to prevent
cold air infi ltration.

C. Gas Connection

NOTE: Have the gas supply line installed in accordance with
local building codes, if any. If not, follow ANSI Z223.1. Instal-
lation should be done by a qualifi ed installer approved and/or
licensed as required by the locality. (In the Commonwealth of
Massachusetts, installation must be performed by a licensed
plumber or gas fi tter.)

Leak test all gas line joints and the gas control valve prior
to and after starting the appliance.

Before making the gas connection, ensure that the appliance
you are installing is designed for the type of gas being
supplied. This information can be found on the Ratings Label
under the appliance. If the appliance has been converted to
propane (LP), the valve cover should have a label stating
that the unit has been converted to propane.

Connect the gas line at the 3/8 in. (9.5mm) pipe connector
on the valve at the back of appliance.

We recommend

connecting the appliance with an approved flex gas line.

If flex gas lines are not approved in your area, you must
connect a hard pipe to the gas hookup.

You must supply a manual shut-off valve in a visible location
within 3 feet (914mm) of the appliance.

WARNING

Fire Risk.
Explosion Hazard.
High pressure will damage valve.
• Disconnect gas supply piping BEFORE

pressure testing gas line at test pressures
above 1/2 psig.

• Close the manual shutoff valve BEFORE

pressure testing gas line at test pressures
equal to or less than 1/2 psig.

WARNING

Verify inlet pressures.
• High pressure may cause overfi re condition.
• Low pressure may cause explosion.
Install regulator upstream of valve if line pressure is
greater than 1/2 psig.

WARNING

Gas Leak Risk.

• Support control when attaching pipe to

prevent bending gas line.

PRESSURE

NG

LP

Minimum Inlet Pressure

5 inches w.c.

11 inches w.c.

Maximum Inlet Pressure

10 inches w.c.

13 inches w.c.

Manifold Pressure on “HI”

3.5 inches w.c.

10 inches w.c.

Advertising
This manual is related to the following products: