Regenerative Braking Torque Limit 1

Program

⇒

Torque

⇒

Torque Limit Settings

This parameter determines the source of the Regenerative Torque Limit
control signal.

If Setting is selected, the value set at

F443

is used for this parameter.

Settings:

1 — V/I
2 — RR
3 — RX
4 —

F443

(setting)

Direct Access Number — F442

Parameter Type — Selection List

Factory Default —

F443

Setting

Changeable During Run — Yes

Regenerative Braking Torque Limit 1 Level

Program

⇒

Torque

⇒

Torque Limit Settings

This parameter provides a value to be used as the Regeneration Torque Limit
#1
if

F443

is selected at parameter

F442

.

Set this parameter to 250% to disable this function.

Direct Access Number — F443

Parameter Type — Numerical

Factory Default — 250.0 (Disabled)

Changeable During Run — Yes

Minimum — 0.00

Maximum — 249.9

Units — %

Power Running Torque Limit 2 Level

Program

⇒

Torque

⇒

Manual Torque Limit Settings

This parameter is used to set the positive torque upper limit for the #2 motor
profile when multiple motors are controlled by a single drive or when a single
motor is to be controlled by multiple profiles.

Direct Access Number — F444

Parameter Type — Numerical

Factory Default — 250.0 (Disabled)

Changeable During Run — Yes

Minimum — 0.00

Maximum — 250.0 (Disabled)

Units — %

Regenerative Braking Torque Limit 2 Level

Program

⇒

Torque

⇒

Manual Torque Limit Settings

This parameter is used to set the negative torque upper limit for the #2 motor
profile when multiple motors are controlled by a single drive or when a single
motor is to be controlled by multiple profiles.

Direct Access Number — F445

Parameter Type — Numerical

Factory Default — 250.0 (Disabled)

Changeable During Run — Yes

Minimum — 0.00

Maximum — 250.0 (Disabled)

Units — %

Power Running Torque Limit 3 Level

Program

⇒

Torque

⇒

Manual Torque Limit Settings

This parameter is used to set the positive torque upper limit for the #3 motor
profile when multiple motors are controlled by a single drive or when a single
motor is to be controlled by multiple profiles.

Direct Access Number — F446

Parameter Type — Numerical

Factory Default — 250.0 (Disabled)

Changeable During Run — Yes

Minimum — 0.00

Maximum — 250.0 (Disabled)

Units — %