H9 ASD Installation and Operation Manual

189

ASD Overload

Program

⇒

Protection

⇒

Overload

This parameter is used to protect the ASD from an overcurrent condition. The
standard overload rating of the H9 ASD is 150% operation for 60 seconds.

This setting allows for the overload protection to be switched from the standard
overload detection means (Thermal Detection and Overload) to thermal
detection only.

Settings:

0 — Thermal Detection + Overload
1 — Thermal Detection Only

The Thermal Detection Only selection is used when multiple devices are
installed horizontally as described on

pg. 15

. If the installation provides for no

space in between the adjacent devices the ASDs must be derated as described in

Figure 31 on pg. 190

.

Direct Access Number — F631

Parameter Type — Selection List

Factory Default — Thermal Detection +
Overload

Changeable During Run — No

F631