H9 ASD Installation and Operation Manual

Torque

— Displays the Output Torque as a percentage of the rated capacity of the H9 ASD.

Torque Reference

— Displays the Torque Reference as a percentage.

Torque Current

— Displays the torque-producing current value.

Excitation Current

— Displays the current value required to produce the excitation field.

PID Feedback

— Provides a status of the PID Real Time Feedback in Hz.

Input Power

— Displays the Input Power in Kilowatts (Kw).

Output Power

— Displays the Output Power in Kilowatts (Kw).

Pattern Group Number

— Displays the active Pattern Run Group Number.

Pattern Group Cycle

— Displays the cycle number of the active Pattern Run Group.

Pattern Group Preset

— Displays the active Preset Speed being run of the active Pattern Run

Group.

Pattern Time

— Displays the remaining time for the active Pattern Run Group.

RR

— Displays the RR input value as a percentage of the full range of the RR value (potentiometer

input).

*

V/I

— Displays the V/I input setting as a percentage of the full range of the V/I value.

Note:

The isolated V/I input terminal may receive Current or Voltage to control the
output speed or the output torque. The input signal type must be selected at SW301
on the Terminal Board.

The V input setting of SW301 is used for the 0 – 10 VDC analog input signal and
the I input setting of SW301 is used for the 0 – 20 mA analog input signal. Either
may be used as a frequency or torque command source. See parameter

F201

for

more information on the setup of this terminal.

On the LCD display the V/I terminal is listed as the VI/II terminal (the additional
letter I is used to indicate “input.”).

RX

— Displays the RX input setting as a percentage of the full range of the RX value (-10 to

+10 VDC input).

RX2 Option (AI1)

— Displays the RX2 input setting as a percentage of the full range of the RX2

value.

Note:

The RX2 function is available on the Expansion IO Card Option 1 option board

(P/N ETB003Z) only.

Trip Code

— Displays None if there are no errors, or displays one of the associated Fault Codes

listed in

Table 14 on page 250

if there is an active Fault (e.g., E = Emergency Off).

Past Trip #1

— This function records and displays the last trip incurred. Subsequent trips will

replace Past Trip #1. As trip records are replaced they are shifted to the next level of the Past Trip
locations until being deleted (i.e., Past Trip #1 is moved to Past Trip #2 and then to #3 until being
shifted out of #4). Once shifted out of Past Trip #4 the record is deleted. If no trips have occurred
since the last reset, None is displayed for each trip record.

Past Trip #2

— Past Trip information.

Past Trip #3

— Past Trip information.

Past Trip #4

— Past Trip information.

Note:

An improper H9 ASD setup may cause some trips — reset the H9 ASD to the
Factory Default settings before pursuing a systemic malfunction (Program

⇒

Utilities

⇒ Type Reset ⇒ Reset to Factory Settings).