170

H9 ASD Installation and Operation Manual

Deceleration Time 4

Program

⇒

Special

⇒

Accel/Decel #1 – #4 Settings

This parameter specifies the time in seconds for the output of the ASD to go
from the Maximum Frequency to 0.0 Hz for the #4 Deceleration profile. The
Accel/Decel pattern may be set using

F502

. The minimum Accel/Decel time

may be set using

F508

.

Note:

A deceleration time shorter than the load will allow may cause
nuisance tripping and mechanical stress to loads. Automatic
Accel/Decel
, Stall, and Ridethrough settings may lengthen the
deceleration times.

Direct Access Number — F515

Parameter Type — Numerical

Factory Default — (ASD-dependent)

Changeable During Run — Yes

Minimum — 0.1

Maximum — 6000

Units — Seconds

Acceleration/Deceleration Pattern 4

Program

⇒

Special

⇒

Accel/Decel #1 – #4 Settings

This parameter enables a user-selected preprogrammed output profile that
controls the acceleration and deceleration pattern for the #4 Accel/Decel
parameter.

Settings:

0 — Linear
1 — S-Pattern 1
2 — S-Pattern 2

Direct Access Number — F516

Parameter Type — Selection List

Factory Default — Linear

Changeable During Run — Yes

Acceleration/Deceleration Switching Frequency 3

Program

⇒

Special

⇒

Accel/Decel Special

This parameter sets the frequency at which the acceleration control is switched
from the Accel #3 profile to the Accel #4 profile during a multiple-acceleration
profile configuration.

Direct Access Number — F517

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — Max. Freq. (

F011

)

Units — Hz

Pattern Operation Selection

Program

⇒

Pattern Run

⇒

Pattern Run

Pattern Run operation is enabled by selecting Seconds or Minutes as a unit of
measure for the Operation Time setting for the selected Preset Speeds.

See Parameter

F523

for more information on Selections and Group Speeds

setup.

Settings:

0 — Disabled
1 — Enabled (units in seconds)
2 — Enabled (units in minutes)

Direct Access Number — F520

Parameter Type — Selection List

Factory Default — Disabled

Changeable During Run — No

Pattern Operation Mode

Program

⇒

Pattern Run

⇒

Pattern Run

This parameter sets the start condition of subsequent Pattern Runs after the
initial Pattern Run has been terminated or has completed its programming.

Settings:

0 — Reset After Stop
1 — Continue After Stop

Direct Access Number — F521

Parameter Type — Selection List

Factory Default — Reset After Stop

Changeable During Run — No

F515

F521