H9 ASD Installation and Operation Manual

79

Type Reset

Program

⇒

Utilities

This feature assists the user when performing fault analysis or by allowing a
quick system setup change when required. Performing a Type Reset results in
one of the following user-selected post-reset configurations.

Settings:

0 — None
1 — 50 Hz Setting
2 — 60 Hz Setting
3 — Reset to Factory Settings
4 — Clear Past Trips
5 — Clear Run Timer
6 — Initialize Typeform
7 — Save User Settings
8 — Restore User Settings
9 — Clear Cumulative Fan Timer
10 — Accel/Decel Time Setting 0.01 – 600.0 Seconds
11 — Accel/Decel Time Setting 0.1 – 6000.0 Seconds
12 — Update EOI Firmware
13 — Set EOI Memory to Default
14 — Save User Settings to EOI
15 — Restore User Settings from EOI

Direct Access Number — F007

Parameter Type — Selection List

Factory Default — None

Changeable During Run — No

Forward/Reverse Run Selection

Program

⇒

Fundamental

⇒

Standard Mode Selection

While operating using the keypad (

F003

is set to EOI Keypad) this parameter

sets the direction of motor rotation. This setting may be changed during
operation. This setting will not override parameter

F311

(Forward/Reverse

Disable).

If either direction is disabled via parameter

F311

, the disabled direction will not

be recognized if commanded by the keypad. If both directions are disabled via
parameter

F311

, the direction command from the keypad will determine the

direction of the motor rotation.

Settings:

0 — Forward
1 — Reverse
2 — Forward (EOI-switchable F/R)
3 — Reverse (EOI-switchable F/R)

Direct Access Number — F008

Parameter Type — Selection List

Factory Default — Forward

Changeable During Run — Yes

Reset

F007

F008