F690, F692, F693 – Toshiba H9 User Manual

Page 206: F691, F700

Advertising
background image

198

H9 ASD Installation and Operation Manual

MON 1 Bias Adjustment

Program

⇒

Terminal

⇒

Analog Output Terminals

This parameter setting is used to ensure that a zero-level input signal produces a
zero-level output at the MON1 terminal.

Set the assigned function of parameter

F672

to zero and then set this parameter

to a zero output.

See parameter

F672

for more information on this setting.

Direct Access Number — F690

Parameter Type — Numerical

Factory Default — 0.0

Changeable During Run — Yes

Minimum — -10.0

Maximum — 100.0

Units — %

MON 2 Voltage/Current Output Switching

Program

⇒

Terminal

⇒

Analog Output Terminals

This parameter is used to set the output signal type of the MON2 output
terminal.

See parameter

F674

for more information on this setting.

Settings

0 — -10V – +10V
1 — 0 – 10V
2 — 0 – 20 mA

Direct Access Number — F691

Parameter Type — Selection List

Factory Default — 0 – 10V

Changeable During Run — Yes

MON 2 Output Gradient Characteristic

Program

⇒

Terminal

⇒

Analog Output Terminals

This parameter sets the output response polarity of the MON2 output terminal.
The MON2 output terminal response may be set to respond inversely (-) or
directly (+) to the input signal.

See parameter

F672

for more information on this setting.

Settings:

0 — Minus (Negative Gradient)
1 — Plus (Positive Gradient)

Direct Access Number — F692

Parameter Type — Selection List

Factory Default — Plus

Changeable During Run — Yes

MON 2 Bias Adjustment

Program

⇒

Terminal

⇒

Analog Output Terminals

This parameter setting is used to ensure that a zero-level input signal produces a
zero-level output at the MON2 terminal.

Set the assigned function of parameter

F674

to zero and then set this parameter

to a zero output.

See parameter

F674

for more information on this setting.

Direct Access Number — F693

Parameter Type — Numerical

Factory Default — 0.0

Changeable During Run — Yes

Minimum — -10.0

Maximum — 100.0

Units — %

Parameter Write Lockout

Program

⇒

Utilities

⇒

Prohibition

This parameter Enables/Disables the Run and Stop keys.

Settings:

0 — Enabled
1 — Disabled

Direct Access Number — F700

Parameter Type — Selection List

Factory Default — Enabled

Changeable During Run — Yes