F681, F676 on pg. 196, F682 – Toshiba H9 User Manual

Page 204: F675, F676, F677

Advertising
background image

196

H9 ASD Installation and Operation Manual

MON2 Terminal Adjustment

Program

⇒

Terminal

⇒

Analog Output Terminals

This parameter is used to set the gain of the MON2 output terminal and is used
in conjunction with the settings of parameter

F674

.

See parameter

F674

for more information on this setting.

Direct Access Number — F675

Parameter Type — Numerical

Factory Default — 512

Changeable During Run — Yes

Minimum — 1

Maximum — 1280

FP Terminal Assignment

Program

⇒

Terminal

⇒

Analog Output Terminals

This parameter sets the functionality of the FP output terminal to any one of the
user-selectable functions listed in

Table 6 on pg. 239

and is enabled at

parameter

F669

.

As the assigned function changes in magnitude or frequency, the pulse count of
the FP output terminal pulse train changes in direct proportion to changes in the
assigned function.

Note:

The duty cycle of the output pulse train remains at 65 ±5.0 µ S.

This parameter is used in conjunction with parameter

F669

and

F677

.

Direct Access Number — F676

Parameter Type — Selection List

Factory Default — Output Frequency

Changeable During Run — Yes

Pulse Output Frequency

Program

⇒

Terminal

⇒

Analog Output Terminals

This parameter scales the FP output terminal by setting the pulses-per-second
output signal of the FP terminal.

See

F676

for more information on this parameter.

Direct Access Number — F677

Parameter Type — Numerical

Factory Default — 3.84

Changeable During Run — Yes

Minimum — 1.00

Maximum — 43.20

Units — Pulses/Second

FM Voltage/Current Output Switching

Program

⇒

Terminal

⇒

Analog Output Terminals

This parameter is used to select the type of output signal provided at the FM
terminal (i.e., voltage or current).

The output voltage and current range is 0 – 10 VDC and 0 – 20 mA,
respectively.

See

F005

for more information on this setting.

Settings:

0 — 0 – 10V
1 — 0 – 20 mA

Direct Access Number — F681

Parameter Type — Selection List

Factory Default — 0–10V

Changeable During Run — No

FM Output Gradient Characteristic

Program

⇒

Terminal

⇒

Analog Output Terminals

This parameter sets the output response polarity of the FM output terminal. The
FM output terminal response may be set to respond inversely (-) or directly (+)
to the input signal.

See

F005

for more information on this setting.

Settings:

0 — Minus (Negative Gradient)
1 — Plus (Positive Gradient)

Direct Access Number — F682

Parameter Type — Selection List

Factory Default — Plus

Changeable During Run — Yes

FP

F675

F682