The rated temperature rise

represents a temperature rise for the motor's

rated current (full laod current).

This value is usually submitted by a motor

manufacturer as test data.

This relay requires setting of the motor's heating time constant and the cooling
time constant. These values are also supplied as the motor data.

When they are

not shown. request them from the motor manufacturer.

As a reference. the standard values of Toshiba motors are shown in Table 6.

Table 6 Heating Time Constant of Motor

(Toshiba Standard Values)

Motor kind

Time constant

(minute)

Totally

Other than totally Heating Cooling

Frame

enclosed

enclosed outer fan TR

I I

TD

outer fan

2 poles

4 pole

or more

355

30

400

355

45

4

450-630

400-630

60

560,

90

710

120