7.4 Detection of Starting Current and Starting Time

The

checks a motor current to detect whether the motor is stopped.

starting, running or overloaded.

The detection conditions are as follows:

Stopped:

the motor current is less than 5% of the motor's rated

current

Starting:

From the time when the motor current exceeds 1.5 times the
motor rated current

as it leaves the stopped condition

until the motor current falls below 1.5 times the motor
rated current.

Running:

Not during the starting period. when the motor current is
higher than 5% of the motor rated current. but lower than a
current that will trigger the overload

function.

(4) Overloaded: Not during the starting period, when the motor current exceeds

the operating value for the overload

function.

L

x IN

I.

(1) Starting current

The starting current is a current value that exists

ms after the relay

has detected that the motor is starting.

The starting current is obtained

by taking an average of five starting currents.

(2) Starting time

The time 2 shown in the diagram above is taken as a starting time.

,

time is obtained by taking an average of five starting times.