21-6: Setting of the allowable motor locking time

Setting depends on the insulation class of the winding.

See

Table 5 (Table Al).

21-T: Setting of the rated temperature rise

=

1.2

Under this condition, the operating point of OL is given by

1.1 x

22-2: Setting of the INST current

This function should be locked when a combination starter is
used as the motor starter.

When switchgear incorporating a circuit breaker is used as the
starter, the following characteristics should be coordinated

during the setting procedure:

Motor starting current
Motor inrush current

overcurrent relay characteristics

22-3: Setting of INST time

This is fixed at 0.05 s.

22-4: Setting of OC current

OC is not for the motor protection but for the protection of
equipment connected to the motor. OC is locked when the
equipment protection is not needed.
When OC is

set to 1.5 (times).

22-5: Setting of OC time

Set time to 0.3 s.

--

-

-

23-2: Setting of unbalance factor

Set to 5%.

23-3: Setting of UC current

UC is not for the motor protection, but for preventing

underload or less of load condition.

When not necessary, it is locked.
When needed, set to 80

It is recommended however that you measure
the no-load current

and set the UC current to 1.2 x

-- 118