23-4: Setting of UC time

Set to 1

24-2: Setting of OCG current

To prevent undesired operation, Set to 10

24-3: Setting of OCG time

Set to 0.1 s.

25-2: Setting of allowable locking time in cold condition

Given value (Consult motor manufacturer>

25-3: Starting current

See motor data.
Or after one start, read screen P4. (See page

25-4: Starting time

Varies per application. (motor,

of starter)

calculate based on motor torque and load .
Or after one start, read screen P4. (See page