1 power supply check, 2 cpu check, 3 program check – Toshiba Programmable Logic Controller V200 User Manual

Page 126

Advertising
background image

Page 118

8.1.1 Power Supply Check

If the PWR (power) LED is not lit after power on, check the following points.

Check the power connection

Connection terminals are correct.

The terminal screws are not loose.

The terminal block is installed securely.

Correct

Check the power voltage

24 VDC; +/- 15%

at the V200’s terminal

Normal

Remove the programmer

If the PW R LED becomes normal, the

port connector

internal supply may be shorted in the

external connections of this port.

Still unlit

Remove the expansion

If the PWR LED is still OFF, the V200

Unit

basic unit may be faulty. Replace the unit.

Lit

Insert the removed expansion

Replace the faulty expansion unit.

Unit one by one to pinpoint

the faulty expansion

8.1.2 CPU Check

If the RUN LED is not lit after power on, check the following points.

Check the position of the

If it is not in R (RUN) position, turn the

mode control switch

switch to R (RUN) position.

Check the ERR (error) LED

If the ERR LED is lit, the V200 CPU PLC
model is in the ERROR mode. Confirm the
error message by connecting the programming

tool.

If only ERR LED is blinking either ladder or
application is invalid. Download the program
again.

Is the RUN & ERR LED blinking ?

Firmware is invalid. Download the firmware again.

8.1.3 Program Check

Check the user program based on the following points if it is running but the operation does not work as intended.

1. Whether duplicated coils are not programmed.

2. Whether a coil device and a destination of a function instruction are not overlapping.

3. Whether the ON/OFF duration of an external input signal is not shorter than the unit’s scan time.

4. Whether a register/device which is used in the main program is not operated erroneously in the interrupt

program.