Toshiba Programmable Logic Controller V200 User Manual

Page 133

Advertising
background image

Page 125

No

Device/register

Name

Function

1

2

3

4

5

6

7

8

9

10

MW01_0

MW01_1

MW01_2

MW01_5

MW01_6

MW01_11

MW01_13

MW01_14

MW01_15

MW02_1

CPU error (down)

I/O error

Program error Clock/calendar

error(alarm) Retentive data

loss/invalid(alarm) System

Watchdog error (down) I/O

mismatch (down)

Analog Power Fail I/O

BCC error (down)

Scan time over (alarm)

ON at error state

ON at error state

ON at error state

ON when clock/calendar data is illegal

ON when retentive data in RAM are invalid

ON at error state

ON at error state

ON at error state

ON at error state

ON when the scan time exceeds 200 ms

ROM Errors:

If the PLC does not have a program ( Firmware / Application / Ladder ) it remains in the wait loop as given in the Flow

Chart. The LEDs are used to indicate these conditions. These errors are not logged in the event history.

No

Condition

Indication

1

2

3

No Firmware or Firmware corrupted.

No Application or Application corrupted.

No Ladder or Ladder corrupted.

RUN LED and ERR LED blinks at one second interval

simultaneously.

ERR LED blinks at one second interval.

ERR LED blinks at one second interval.

Diagnosis Registers for Serial and Ethernet Communication channels:

Following system registers and system coils can be used for the control and diagnosis of communication channels:

Register / Coil

Tag Name

Read / Write

Description

SW0003_14

COM1 Status

Read only

0 = Communication Error

1= Communicating with Master

SW0003_15

COM2 Status

Read only

0 = Communication Error

1= Communicating with Master

SW0003_13

COM3 Status

Read only

0 = Communication Error

1= Communicating with Master

SW0018

COM1 failed node

reconnect time (Sec)

Read/write

Shows time in sec recover the communication

with failed nodes for port1.the default value is

60Sec

SW0019

COM2 failed node

reconnect time (Sec)

Read/write

Shows time in sec recover the communication

with failed nodes for port1.the default value is

60Sec

SW0022

COM3 failed node

reconnect time (Sec)

Read/Write

Shows time in sec recover the communication

with failed nodes for port3.the default value is

60Sec

S0021

COM1 failed node

reconnect control

Read/write

If this bit is set communication with the failed

nodes is detected after scan time SW0018 for

port1.By default : ON