No.

Event

Info1

Info 2

Info 3

Info 4

Special

Device

Meaning and
countermeasures

Check at

1

Retentive
Data Loss
Error

MW01_6

In the power-up initialization,
data invalidity of RAM (back-
up area) has been detected.

If retentive registers are used,
these validity are not guarant-
eed. (No error down)

Only Power-On

2

Clock-cal-
endar error

MW01_5

The data of built-in calendar
LSI is illegal.(No error down)
Set the date and time.

Only Power-On

4

I/O

mismatch

slot

No.

Unit

Type

MW01_1

MW01_13

The I/O allocation information
and the actual I/O configuration
are not identical.(Error down)
Check the I/O allocation and

the option card mounting status

Only Power-On

5

I/O BCC

error

Unit

No.

Register

No.

MW01_1

MW01_15

I/O bus parity error has been
detected in data read/write for
I/O modules. An abnormality
has been detected in I/O bus
checking. (Error down)I/O No
answer. (Error down) Check
the expansion cable connect-

ion and the I/O module mounting
status.

Each main loop

scan

The errors in the PLC can be categorized as below:

1.

CPU error:

a. System watchdog Reset (WDT Error)

If there is error in this category the CPU error flag ( MW01_0 device) sets along with corresponding device of
the error. So for WDT error MW01_11 device sets.

2.

I/O Error:

a. I/O mismatch error
b. I/O bcc error.

If there is error in this category the I/O error flag ( MW01_1 device) sets along with corresponding device of
the error. So for I/O mismatch error MW01_13 device sets and for I/O bcc error MW01_15 device sets.

3.

Program Error:

a. Scan Time Over error

If there is error in this category the I/O error flag ( MW01_2 device) sets along with corresponding device of
the error. So for Scan Time Over error MW02_1 device.

4.

Other Errors:

a. Clock calendar error

b. Retentive Data Loss error

For Clock calendar error MW01_5 device sets and for Retentive Data Loss error MW01_6 device sets

Above error conditions are checked either in each main loop scan or only at power up. This is mentioned in the
following table.

The configuration devices (M) and configuration registers (MW) are used for special purposes.

Error Messages and related information: