3 single phase speed counter, Single phase speed-counter – Toshiba Programmable Logic Controller V200 User Manual

Page 98

Advertising
background image

Page 90

5.3 Single Phase Speed Counter

When the count input is changed from OFF to ON, the count value is increased by 1. When the count value reaches
the set value, the count value is reset to 0, and I/O interrupt program is activated (if the interrupt enable flag is ON).
The count value is reset to 0 when the reset input comes ON. This counter operation is enabled while the soft-gate is
ON. The count value is reset to 0 when the soft-gate is changed from ON to OFF. The set value is set internally at

the timing of the soft-gate changing from OFF to ON. When the soft-gate is OFF, count value can be changed by
writing the data into the set value register and setting the count preset flag to ON. The count value range is H0000

0000 to HFFFF FFFF (32-bit data).

Hardware Condition:

Count input (IP 1 and IP 2) (X000 and X001)

ON/OFF pulse width: 10 micro or more (max. 50 kHz)
Reset input (X002 and X003)

ON/OFF duration: 2 ms or more

Related Registers:

Function

Register/device

Remarks

Channel 1

Channel 2

Count input

IP 1 (X000)

IP 2 (X001)

Reset input

IP 3 (X002)

IP 4 (X003)

Set value

MW12 SW13

MW14 MW15

Data range: H0000 0000 to HFFFF FFFF

Count value

MW16 MW17

MW18 MW19

Soft-gate

M320

M328

Operation is enabled when ON

Interrupt enable

M322

M330

Interrupt is enabled when ON

Count preset

M323

M331

Used to preset the counter value

Note1:

When both the channels are configured in high speed mode, IP1 to IP4 cannot be used as normal input devices.
However, if either one channel is configured in high speed mode, the inputs for other channel can be used as normal
input devices.

Note2:

Two words are used for storing the double word (32bit) count/set values. Lower word will contain Lower 16bit value
and Higher word will contain higher 16 bit. This register storage scheme is applicable for all the modes.

value. Eg.

Count value

:

MW16,MW17

So if count value is (Hex) 87654321

MW16 = 4321 (Hex)
MW17= 8765 (Hex)

Note3:

Input 3 and input 4 are used as reset inputs for count inputs 1 and 2. So do not use input 3 and 4 as normal inputs
when PLC is configured in this mode.

Interrupt assignment

Channel 1 --- I/O interrupt program #1

Channel 2 --- I/O interrupt program #2