Toshiba Programmable Logic Controller V200 User Manual

Page 92

Advertising
background image

Page 84

Channel Type Selection Values Table:

Use the following values in the Input and output channel type select register to configure the corresponding channel
to particular type.

e.g. If you want to configure the Input channel 3 of GAD208**S model as ( 0 – 10 V ) type, then move value 19 in
MWxx16 configuration register. Here xx digital denotes the slot number in which the GAD208**S model is
connected to PLC. The Conversion Enable Flag should be one to start the conversion (A to D or D to A).

Input Channel Type

Value

Not Defined

0

mV( 0 - 100 mV )

1

mV( 0 - 50 mV )

3

mA( 0 - 20mA )

5

mA( 4 - 20mA )

7

Voltage ( 0 - 10V )

19

Voltage ( 1 - 5V )

20

RTD PT-100 (alpha1)

9

RTD PT-100 (alpha2)

10

RTD PT-1000

21

Thermocouple (B-Type)

11

Thermocouple (R-Type)

12

Thermocouple (S-Type)

13

Thermocouple (E-Type)

14

Thermocouple (J-Type)

15

Thermocouple (K-Type)

16

Thermocouple (N-Type)

17

Thermocouple (T-Type)

18

Output Channel Type

Value

Not Defined

0

mA( 4 - 20mA )

1

Voltage ( 0 - 10V )

2