8.1.4 Input Check

If the program is running but the external input signal is not read normally, check the following points:

If not, check the input voltage at the

V200’s input terminals.

If the voltage is not normal, check the input
device and the cable.

If the voltage is normal, the V200’s

input circuit may be faulty.

Connect the programming

If the monitored X device state is identical

tool, and monitor the

to the state of the input status LED, the

corresponding X device state

cause may lie in the user program or in the

in RUN mode

environment.

Not normal

Check whether the X device

If it is forced, release the force designation

is forced or not

then execute the EEPROM write

operation.

Not forced

In force run mode physical inputs and

outputs are not updated.

Execute the automatic I/O

Download the application now

allocation, and check whether

and execute ladder.

the I/O allocation table is now

identical to the actual I/O

configuration

No

Check the expansion unit

Replace the faulty unit or else the

Hardware one by one

V200 CPU may be faulty.

the expansion rack ?