2 daily checks, Daily checks, Caution – Toshiba Programmable Logic Controller V200 User Manual

Page 137

Advertising
background image

Page 129

9.2 Daily Checks

CAUTION

1. Pay special attention during the maintenance work to minimize the risk of electrical

shock.

2. Turn off power immediately if the V200 CPU or related equipment is emitting smoke

or burning. Operation under such situation can cause fire or electrical shock.

To maintain the system and to prevent troubles, check the following items on daily basis.

Item

Check

Corrective measures

Status LEDs

PWR
(power)

Lit when internal 3.3 V

is normal.

If the LEDs are not normal, see

Troubleshooting.

RUN

Lit when operating
normally.

FLT (fault)

Not lit when operating
normally.

Mode control
switch

Check that the mode control switch is in
R (RUN) side. Normal operation is
performed when this switch is in R

(RUN) side.

Turn this switch to R (RUN) side.

Input LEDs

Lit when the corresponding input is ON.

• Check that the input terminal screw

is not loose.

• Check that the input terminal block is

not loose.

• Check that the input voltage is within

the specified range.

Output LEDs

Lit when the output is ON and the
corresponding load should operate.

• Check that the output terminal

screw is not loose.

• Check that the output terminal

block is not loose.

• Check that the output voltage is

within the specified range.