Operation and Description of Instrument Function

Average Temperature/Water Bottom Sensor and Converter

38

Installation and Operations Manual

VH69 Ref Voltage

Item type: read and write

Default: 200

Range: 0 ~ 255

This parameter is the setpoint for the 4532 ATC power supply failure alarm. The

4532 ATC operates with a minimum 16 VDC supply voltage via the multi-drop HART

loop under normal operating conditions. The 4532 ATC transmits an error message

when the supply voltage drops below 16 VDC. The default value of 200 is equivalent to

16 VDC.

8.1.8

Temperature Adjustment: VH70 ~ VH79

VH70 Element Select

Item type: select

Range: 0 ~ 19

Allows selection of individual temperature elements for adjustment (0 = #1 element,

5 = #6 element, 19 = reference 100 Ohm resistor). Detailed values and parameters of

the selected element can be shown in:

VH71 "Zero Adjust"

VH73 "Temperature X"

VH74 "Position X"

VH75 "Resistance X"

VH76 "Resistance Adj"

VH71 Zero Adjust

Item type: read and write

Default: 0

Range: -1000.0 ~ 1000.0

Zero adjustment of the individual element selected at VH70. This value can be adjusted

when the measured temperature of the selected element has a minor offset value as

compared to a precision reference thermometer.

For example: Selected element #2 indicates 25.4 °C. The reference thermometer

indicates 25.2 °C. Enter "-0.2" in VH71. Element #2 now has a constant offset applied to

the raw measurement.

VH72 Adjust Span

Item type: read and write

Default: 1

Range: 0.8 ~ 1.2

This span adjustment applies to all installed temperature elements. This parameter is

multiplied by the raw measurement for each individual element to calculate the

calculated temperature for each individual element.

Note!

All of displayed individual temperature values are calculated based on the following
formula.