Connection diagram, Waterpik technologies inc, Page 8 – Waterpik Technologies LD User Manual

Page 10

Advertising
background image

Page 8

WATERPIK TECHNOLOGIES INC.

Figure 7. LG Connection/Schematic Wiring Diagram

2F-2. Auxiliary Time Clock Wiring (LD)

If you install a time clock to control the filter

pump operation, it is recommended that the time clock

have its own low voltage (Fireman’s) switch to turn off

the heater before turning off the pump. The switch

should shut off the heater about 15 minutes before the

filter pump shuts off. This will allow for a more

efficient operation by removing any residual heat

contained in the heat exchanger back to the pool.

Caution

Do not provide power to the heater from the

high voltage side of the time clock. Doing so

may cause damage to the heater or

surrounding plumbing.

0,//,92/7 +($7(5 :,5,1* ',$*5$0

Y

Connection
Diagram

BK

TH

PP

Y

Y

W

PP/TH

Pilot

Gen

R

W

Piezo

Sparker

Y

W

H0166000G

Pilot

Piezo

Sparker

R

Y

Y

BK

PP

PP

W

PP/TH

Valve

Operator

Coil

W

Y

To Pilot

Generator

Pilotstat

Power

Unit Coil

IF ANY OF THE ORIGINAL WIRE AS

SUPPLIED WITH THE HEATER MUST BE
REPLACED, APPLI ANCE WIR ING
MATERIAL RATED FOR 105°C MUST BE
USED. WHERE MARKED THUS

APPLIANCE WIRING MATERIAL FOR
200°C MUST BE USED.

CIRCUIT

TH/PP

TH

_

+

BK

BK -

Black

W -

White

Y

-

Yellow

R -

Red

O -

Orange

On

TEMP. CONTROL

Min

Max

BK

Y

BK

O

O

Off

Y

High

Limit

Switch

Pressure

Switch

Fusible

Link

Fireman

Switch

Connection

High

Limit

Switch

W

W

W

W

BK

Advertising