Waterpik Technologies LD User Manual

Page 8

Advertising
background image

Page 6

WATERPIK TECHNOLOGIES INC.

7.

Disconnect the heater and its individual shutoff

valve from the gas supply system during pressure

testing of the system at pressures higher than 1/2

pounds per square inch (psi) (3.45 kilopascals

[kPa]). If the test pressure is equal to or less than

1/2 psi (3.45 kPa), close the manual shutoff valve

on the heater during the piping pressure test.

Caution

Permanent damage to the gas valve will occur

if the following procedures are not followed.

8.

If the gas supply pressure is less than required,

check for undersized pipe between the meter and

the heater, a restrictive fitting, or an undersized

gas meter. Gas supply pressures to the heater are

listed in Table 4.

NOTE: The maximum inlet gas pressure must

not exceed the specified value. The minimum value

listed is for the purpose of input adjustment. Refer to

Table 4.

9.

Before operating the heater, test the complete gas

supply system and all connections for leaks using

a soap solution. Do not use an open flame.

Caution

Some leak test solutions (including soap and

water) may cause corrosion or stress cracking.

Rinse the piping with water after testing.

2E-2. Special Precautions for Propane

Gas

Liquefied petroleum (LP) gas is heavier than air.

Therefore, do not install pool heaters using LP gas in

pits or locations where gas might collect. Locate

heaters a safe distance from LP gas storage and filling

equipment. Consult local codes and fire protection

authorities about specific installation restrictions.

5.

Install a sediment trap (drip leg) ahead of the gas

controls (see Figure 5). Fit the trap with a

threaded cap which can be removed for cleaning.

6.

Install a manual gas shutoff valve for service and

safety. Do not use a restrictive gas cock. DO

NOT USE FLEXIBLE GAS PIPING.

2F. Electrical Wiring

Caution

Label all wires prior to disconnection when

servicing controls. Wiring errors can cause

improper and dangerous operation.

Verify proper operation after servicing.

Attention

Au moment de l'entretien des commandes,

étiquetez tous les fils avant de les débrancher.

Des erreurs de câblage peuvent entraîner un

fonctionnement inadéquat et dangereux.

2F-1. General Information (LD Only)

Wiring connections must be made exactly as

shown in the wiring diagram found on the inside of the

heater (see Figures 6 and 7 for typical examples) . The

heater must include a definite means of grounding.

There is a bonding lug on the right side of the heater,

where a bond wire must be attached.

The heater comes factory-wired intended for

use with 240 Volt, 60 Hz AC field electrical supply.

To use 120 Volt, 60 Hz AC requires rewiring of the

heater. This should be done by a certified electrician

only, as with all wiring. To wire the heater for 120

Volt, 60 Hz AC, follow the alternate 120V wiring

method depicted in Figure 6. Additionally, the ignition

control module must be rewired. The wire from the

terminal marked IGN/240 must be removed from that

terminal and placed on the terminal marked IGN/120.

Electrical wiring must be in accordance with the

latest edition of the National Electric Code (NEC),

ANSI/National Fire Protection Association (NFPA)

70, unless local code requirements indicate otherwise.

To wire the Laars Lite 2 model LD heater to a

120V or 240V /60 Hertz (Hz) electrical source:

1.

Remove the screw located to the lower right side

of the transformer and open the hinged cover of

the wiring enclosure.

2.

Connect the wires from the power source to the

leads on the right side of the heater in the space

behind the ignition control (see Figure 8). Be sure

to follow the wiring diagram on page 7 to config-

ure the transformer for the correct input voltage.

3.

Attach the ground wire to the green ground screw

located on the back panel of the wiring enclosure.

4.

Close the cover of the wiring enclosure and

replace the screw to hold it in place.

5.

Connect a bonding wire (8 ga copper) to the

bonding lug on the right side of the heater.

NOTE: No external junction box is required.

Table 4. Gas Supply Pressure Requirements

Supply Pressure

Natural Gas

Propane Gas

Water Column

in. (mm)

in.

(mm)

Minimum

5.5 (140)

10.0 (254)

Maximum

10.0 (254)

14.0 (356)

Advertising