WATERPIK TECHNOLOGIES INC.

2G-7. Automatic Flow Control Valve

The automatic flow control valve maintains the

proper flow through the heater at rates up to approxi-

mately 125 Gallons Per Minute (GPM) (474 liters per

minute [LPM]). If the system filter-flow rate is higher

than approximately 125 GPM (474 LPM), install a

manual bypass valve (see Figure 20), then perform a

temperature rise test (see Section 2G-8) and adjust the

flow using the bypass valve until the proper tempera-

ture rise is obtained.

2G-8. Temperature Rise

A temperature rise test confirms proper water

flow through the heater. The temperature rise is the

difference between the temperature of the pool or spa

water before and after heating, as measured in the

header. Perform the following temperature rise test

when the installation is complete:
1.

Make sure the pool filter is clean.

2.

Set the rotary switch (LD) or rocker switch (LG)

on the temperature control panel (see Figure 18)

to OFF.

3.

Turn the filter pump off.

4.

Remove the drain plug located on the inlet/outlet

header of the heater and replace it with a Pete's

plug (see Figure 17).

5.

Insert a pocket thermometer (see Figure 17)

through the Pete's plug into the header.

Figure 18. Temperature controls.

Figure 19. Pressure switch adjustment.

6.

Turn the filter pump on and wait 3 minutes. The

heater remains off. This allows water from the

pool to reach the heater.

7.

Record the temperature indicated by the ther-

mometer (cold water).

8.

Turn the heater ON following the lighting in-

structions found on the inside of the heater.

9.

Allow the heater to run for about 3 minutes.

Record the new temperature reading (heated

water).

10. Subtract the first temperature reading (cold

water) from the second temperature reading

(heated water). The difference between the two

readings is the temperature rise. The temperature

rise should be within the range shown in Table 6.

a) Model LD Temperature Control

b) Model LG Temperature Control

NOTE: Heater should not be allowed to fire on

low speed.

4.

Turn rotary switch (LD) or rocker switch (LG) to

ON. Heater should start.

5.

Pry out the top rubber dust plug on the top of the

pressure switch.

6.

Use a 7/32 inch (5.55 mm) Allen wrench to turn

the adjustment screw very slowly clockwise until

the heater goes off (see Figure 19).

7.

Slowly turn the pressure switch adjustment screw

counterclockwise one-quarter turn. The heater

should come back on.

8.

Check the adjustment by turning the filter pump

OFF. The heater should shut off immediately. If

it does not, restart the filter pump and repeat

Steps 6 and 7. Check the adjustment again.

9.

Return the pool temperature control to the desired

temperature.

Minimum

Minimum

Maximum

Size

GPM (LPM)

°F

(°C)

°F

(°C)

125

20

(76)

27

(15)

36

(20)

175

20

(76)

33

(19)

42

(24)

250

25

(95)

33

(19)

42

(24)

325

30

(114)

28

(16)

38

(21)

400

30

(114)

30

(17)

39

(22)

Table 6. Temperature Rise and Minimum Flow Rates