Waterpik Technologies LD User Manual

Page 15

Advertising
background image

Model LG & LD Pool and Spa Heater

Page 13

•

When chemical feeders are used, plumb the

feeder downstream of the heater and install an in-

line check valve between the heater and the feeder

(a minimum of 18" is required between the heater

and the check valve).

•

Never deposit chemicals directly in the pool

skimmer.

2G-4a. Water Chemistry

Proper chemical balances are necessary for

sanitary bathing conditions as well as ensuring your

heater's long life. Be sure to keep your chemical levels

within the values indicated in Table 7. Waterpik

Laars does not warrant heat exchangers damaged

by corrosive chemical levels or excess dissolved

solids in pool or spa water.

For spas, it is also necessary to perform water

changes in addition to chemical treatment. It is recom-

mended to change the spa water every 60 days for light

usage and every 30 days if usage is heavy.

2G-6. Adjusting the Pressure Switch

Caution

The pressure switch should be adjusted to turn

the heater off when the pump is off. Setting

the switch to close at too low of a flow can

damage the appliance. Adjust the switch to

turn the heater off, not on.

The pressure switch is preset at the factory for

activation at 2 psi (14 kPa). Adjust the pressure switch

only if any part of the filter system piping is 3 feet

(0.91 m) or more above the top of the heater jacket.

Do not adjust the pressure switch if the heater is

installed more than 15 feet (4.57 m) below or 6 feet

(1.83 m) above the pool surface. Consult your local

Waterpik Laars representative for recommendations.

On some installations, the piping from the heater

to the pool is very short. The back pressure could be

too low to trigger the pressure switch. If this happens,

it may be necessary to install a directional fitting or

elbows where the return line enters the pool. This will

increase back pressure enough for the heater to operate

properly.

Make sure the pool filter is clean before making

any pressure switch adjustment: A dirty filter will

restrict the water flow and the pressure switch cannot

be adjusted properly. To adjust the pressure switch:
1.

Set the control panel rotary switch (LD) or the

control panel rocker switch (LG) to the OFF

position (see Figure 18).

2.

Set the Pool temperature control to the Max

position.

3.

Turn filter pump on. If a two-speed pump is used,

make sure it is at high speed.

Table 7. Mineral Concentration Levels

Test

Recommended Level

Free chlorine

1.0 to 3.0 ppm

Bromine

3.0 to 5.0 ppm

pH

7.2 to 7.8

Total alkalinity (TA)

80 to 120 ppm

Calcium hardness (CH)

200 to 400 ppm

Langelier saturation index (LSI) -0.5 to +0.5
Total dissolved solids (TDS)

Less than 2000 ppm

Cyanuric acid

30 to 150 ppm

Copper

0 ppm

2G-5. Pressure Relief Valve

A pressure relief valve is not furnished with the

Laars Lite 2 heater. However, it is recommended that a

pressure relief valve be installed and may even be

required by local codes.

To install a pressure relief valve, remove the 3/4

inch (19 mm) brass plug located on the top of the inlet/

outlet header (see Figure 17). Install the pressure relief

valve in the threaded hole from which the plug was

removed. The pressure rating of the valve should be at

or below the lowest working pressure of any compo-

nent in the filter system. Any pressure relief valve

installed must comply with provisions of the Standard

described in ANSI Z21.22 for the United States, or

CAN1-4.6 in Canada.

Figure 17. Thermometer and pressure relief valve.

Advertising