Watlow Electric Integrated Controller User Manual Rev C EZ-ZONE PM User Manual

Page 14

Advertising
background image

Wa t l o w E Z - Z O N E

®

P M I n t e g r a t e d C o n t r o l l e r

1 2

C h a p t e r 2 I n s t a l l a n d W i r e

Slot C

Terminal Function

Configuration

98
99

power input: ac or dc+
power input: ac or dc-

all

CC
CA
CB

Standard Bus or Modbus RTU EIA-485 common
Standard Bus or Modbus RTU EIA-485 T-/R-
Standard Bus or Modbus RTU EIA-485 T+/R+

Standard Bus or Modbus
PM6 _ _ _ _-1 _ _ _ A _ _

CF

CD
CE

Standard Bus EIA-485 common
Standard Bus EIA-485 T-/R-
Standard Bus EIA-485 T+/R+

PM6 _ _ _ _-(A, 2 or 3) _ _ _ A _ _

B5
D6
D5

digital input-output common
digital input or output 6
digital input or output 5

PM6 _ 2 _ _-_ _ _ _ A _ _
PM6 _ 4 _ _-_ _ _ _ A _ _

Terminal Definitions for Slot C.

Slot A

Slot B

Slot C

or

Output 1

O

utput 2

Input 1

Output 3

O

utput 4

Input 2

Power

485 Comms

Dig I/O 5 & 6

Communications

Slot B

Controller

Power Supply

12 to 40V

Î (dc)

24 to 28V

Å (ac)

85 to 264V

Å (ac)

Safety Isolation

Safety Isolation

No Isolation

No Isolation

Low-voltage

Isolation

Low-voltage

Isolation

Low-voltage

Isolation

Low-voltage

Isolation

Low voltage power bus

and

internal bus

Digital Inputs and

Outputs 5 & 6

Switched DC, Open

Collector, Process Outputs

Analog Input 1

Analog Input 2

Mechanical Relay,

Solid-state Relay &

No-arc Relay Outputs

EIA-485

Communications Port

RS-232/EIA-485

Communications Port

Ethernet

Communications Port

Low-voltage Isolation: 42V peak
Safety Isolation: 1,528V

Å (ac)

No Isolation

PM Integrated isolation blocks.