Display

Parameter name

Description

Set-

tings

Range

Default

Appears If

[``Ai] [```1] [```2]
[oPEr] [``Ai] [``Ai]
Analog Input Menu Analog Input 1 or

Analog Input 2

(input 2 appears if PM6 _ _ _ _-_ [R, T or L] _ _ A _ _)

[`Ain]
[ Ain]

Analog Input (1 or 2)
Process Value

View the process value.

-1,999.000 to 9,999.000°F or units

-1,128.000 to 5,537.000°C

always

[`i;Er]
[ i.Er]

Analog Input (1 or 2)
Error Status

View the cause of the most recent error. If the
[Attn] message is [Er;i1] or [Er;i2], this param-
eter will display the cause of the input error.

[nonE] None
[OPEn] Open
[Shrt] Shorted
[`E;M] Measurement Error
[E;CAL] Bad Calibration Data
[Er;Ab] Ambient Error
[E;;Rtd] RTD Lead Resistance Error

None

always

[`i;Ca]
[ i.CA]

Analog Input (1 or 2)
Calibration Offset

Offset the input reading to compensate for lead
wire resistance or other factors that cause the in-
put reading to vary from the actual process value.

-1,999.000 to 9,999.000°F or units

-1,110.555 to 5,555.000°C

0.0

always

[`dio] [```5]

[```6]

[oPEr] [`dio]

[`dio]

Digital Input/

Digital Input or

Digital Input or

Output Menu

Output 5

Output 6

(menu appears if PM6 _ [2 or 4] _ _-_ _ _ _ A _ _)

[`do;S]
[ do.S]

Digital Output (5 or 6)
Output State

View the state of this output.

[``on] On
[`off] Off

always

[`Ei;S]
[ Ei.S]

Digital Input (5 or 6)
Event Input Status

View this event input state.

[iACt] Inactive
[`ACt] Active

always

[ LiM]
[oPEr]
Limit Menu

(menu appears if PM6 _ _ _ _-_ L _ _ AAA)

[`LL;S]
[ LL.S]

Limit
Low Set Point

Set the low process value that will trigger the
limit.

-1,999.000 to 9,999.000°F or units

-1,128.000 to 5,537.000°C

0.0°F or

units

-18.0°C

Limit Sides (Set-

up Page) is not
set to High.

[`Lh;S]
[ Lh.S]

Limit
High Set Point

Set the high process value that will trigger the
limit.

-1,999.000 to 9,999.000°F or units

-1,128.000 to 5,537.000°C

0.0°F or

units

-18.0°C

Limit Sides (Set-

up Page) is not
set to Low.

[Mon]
[oPEr]
Monitor Menu

[C;MA]
[C.MA]

Monitor
Control Mode Active

View the current control mode.

[`off] Off
[AUto] Auto
[MAn] Manual

always

[`h;Pr]
[ h.Pr]

Monitor
Heat Power

View the current heat output level.

0.0 to 100.0%

0.0

always

[`C;Pr]
[ C.Pr]

Monitor
Cool Power

View the current cool output level.

-100.0 to 0.0%

0.0

always

[`C;SP]
[ C.SP]

Monitor
Closed Loop Working Set Point

View the set point currently in effect.

-1,999.000 to 9,999.000°F or units

-1,128.000 to 5,537.000°C

75°F or

units

24°C

always

[`Pu;A]
[ Pv.A]

Monitor
Process Value Active

View the current filtered process value using the
control input.

-1,999.000 to 9,999.000°F or units

-1,128.000 to 5,537.000°C

always

Note: Some values will be rounded off to fit in the four-character display. Full values can be read with other interfaces.

If there is only one instance of a menu, no submenus will appear.