Watlow Electric Integrated Controller User Manual Rev C EZ-ZONE PM User Manual

Page 44

Advertising
background image

Wa t l o w E Z - Z O N E

®

P M I n t e g r a t e d C o n t r o l l e r

4 2

C h a p t e r 6 S e t u p P a g e

Dis-

play

Parameter Name

Description

Set-

tings

Range

Default

Appears If

[`C;Si]
[ C.Si]

Current
Source Output Instance

Select which output instance the current
transformer will monitor.

1 to 6

1 (if not pro-

cess)

2 (otherwise)

always

[`FUn]
[`Set]
Function Key Menu

[`Leu]
[ LEv]

Function Key
Level

Select what state the Function Key will be
in at startup.

Pressing the Function Key will toggle the

selected action.

[high] High
[Low] Low

High

always

[``Fn]
[ Fn]

Function Key

Digital Input Function

Program the EZ Key to trigger an action.

Functions respond to a level state change

or an edge level change.

[none] None
[idLE] Idle Set Point Enable

(level)

[tUnE] Tune (edge)
[ALM] Alarm Reset (edge)
[`SiL] Silence Alarms (edge)
[MAn] Manual/Auto Mode

(level)

[`oFF] Control Outputs Off

(level)

[`r;En] Remote Set Point En-

able (level)

[P;LoC] Lock Keypad (level)
[`F;AL] Force Alarm (level)
[`t;dA] TRU-TUNE+

®

Dis-

able (level)

[`AoF] Alarm Outputs &

Control Loop Off (level)

[USr;r] Restore User Settings

(edge)

[P;diS] Profile Disable (level)
[P;hoL] Profile Hold/Resume

(level)

[ProF] Profile Start Number

(edge)

[P;StS] Profile Start/Stop

(level)

[LMr] Limit Reset (edge)

None

always, but only the
available features can be
selected.

[``Fi]
[ Fi]

Function Key

Instance

Select which instance the EZ Key will af-
fect. If only one instance is available, any
selection will affect it.

0 All Instances (except Pro-

file)

(For example, if Digital Func-

tion is set to Silence Alarms
and Function Instance is set
to 0, then the digital input
would silence all alarms.)

1 to 4

0

there is more than one

instance of the Digital
Input Function selec-
tion.

[gLbL]
[`Set]
Global Menu

[`C_F]
[ C_F]

Global
Display Units

Select which units will be displayed.

[```F] °F
[```C] °C

°F

always

[AC;LF]
[AC.LF]

Global
AC Line Frequency

Set the frequency to the applied ac line
power source.

[``50] 50 Hz
[``60] 60 Hz

60 Hz

always

Note: Some values will be rounded off to fit in the four-character display. Full values can be read with other interfaces.

If there is only one instance of a menu, no submenus will appear.

Advertising