Watlow Electric Integrated Controller User Manual Rev C EZ-ZONE PM User Manual

Page 32

Advertising
background image

Wa t l o w E Z - Z O N E

®

P M I n t e g r a t e d C o n t r o l l e r

3 0

C h a p t e r 5 O p e r a t i o n s P a g e

Display

Parameter name

Description

Set-

tings

Range

Default

Appears If

[Loop]
[oPEr]
Loop Menu

[`r;En]
[ r;En]

Loop
Remote Enable

Switch control to the remote set point.

[``no] No
[`YES] Yes

No

PM6 _ _ _ _-_ (R

)

_ _ A A A

[`r;ty]
[ r.ty]

Loop
Remote Set Point Type

Select how the remote set point will be deter-
mined.

[AUto] Auto (closed loop)
[MAn] Manual (open loop)

Auto

Remote Enable

is set to Yes.

[`C;M]
[ C.M]

Loop
Control Mode

Select the method that the controller will use to
control.

[`off] Off
[AUto] Auto (closed loop)
[MAn] Manual (open loop)

Auto

always

[A;tSP]
[A.tSP}

Loop
Autotune Set Point

Set the set point that the autotune will use, as a
percentage of the current set point.

50.0 to 200.0%

90.0

Heat Algorithm

or Cool Algo-
rithm (Setup
Page) is set to
PID.

[`AUt]
[ AUt]

Loop
Autotune Request

Start an autotune. While autotune is active, the
Home Page will display

[Attn] [tUn1]. When

the autotune is complete, the message will clear
automatically.

[``no] No
[`YES] Yes

No

Heat Algorithm

or Cool Algo-
rithm (Setup
Page) is set to
PID.

[`C;SP]
[ C.SP]

Loop
Closed Loop Set Point

Set the set point that the controller will automati-
cally control to.

Low Set Point to High Set Point

(Setup Page)

75.0°F or

units

24.0°C

always

[`id;S]
[ id.S]

Loop
Idle Set Point

Set a closed loop set point that can be triggered by
an event state.

Low Set Point to High Set Point

(Setup Page)

75.0°F or

units

24.0°C

always

[`h;Pb]
[ h.Pb]

Loop
Heat Proportional Band

Set the PID proportional band for the heat outputs.

0.001 to 9,999.000°F or units

-1,110.555 to 5,555.000°C

25.0°F or

units

14.0°C

Heat Algorithm

(Setup Page) is
set to PID.

[`h;hy]
[ h.hy]

Loop
Heat Hysteresis

Set the control switching hysteresis for on-off con-
trol. This determines how far into the “on” region
the process value needs to move before the output
turns on.

0.001 to 9,999.000°F or units

-1,110.555 to 5,555.000°C

3.0°F or

units

2.0°C

Heat Algorithm

(Setup Page) is
set to On-Off.

[`C;Pb]
[ C.Pb]

Loop
Cool Proportional Band

Set the PID proportional band for the cool outputs.

0.001 to 9,999.000°F or units

-1,110.555 to 5,555.000°C

25.0°F or

units

14.0°C

Cool Algorithm

(Setup Page) is
set to PID.

[`C;hy]
[ C.hy]

Loop
Cool Hysteresis

Set the control switching hysteresis for on-off con-
trol. This determines how far into the “on” region
the process value needs to move before the output
turns on.

0.001 to 9,999.000°F or units

-1,110.555 to 5,555.000°C

3.0°F or

units

2.0°C

Cool Algorithm

(Setup Page) is
set to On-Off.

[``ti]
[ ti]

Loop
Time Integral

Set the PID integral for the outputs.

0 to 9,999 seconds per repeat

180.0 sec-

onds per
repeat

Heat Algorithm

or Cool Algo-
rithm (Setup
Page) is set to
PID.

[``td]
[ td]

Loop
Time Derivative

Set the PID derivative time for the outputs.

0 to 9,999 seconds

0.0

seconds

Heat Algorithm

or Cool Algo-
rithm (Setup
Page) is set to
PID.

Note: Some values will be rounded off to fit in the four-character display. Full values can be read with other interfaces.

If there is only one instance of a menu, no submenus will appear.

Advertising