Wa t l o w E Z - Z O N E

®

P M I n t e g r a t e d C o n t r o l l e r

3 7

C h a p t e r 6 S e t u p P a g e

Dis-

play

Parameter Name

Description

Set-

tings

Range

Default

Appears If

sp;ll
[SP.LL]

Limit
Set Point Limit Low

Clamp the operational limit low maximum
setting to this value.

-1999.000 - 9999.000

-1999.000

always

[`L;it]
[ L.it]

Limit
Integrate

In a limit state the controller will turn off
the outputs, terminate an active profile
and freeze PID and TRU-TUNE+

®

calcula-

tions.

[``no] No
[`YES] Yes

No

always

[ Loop]
[`Set]
Loop Menu

[`h;Ag]
[ h.Ag]

Loop
Heat Algorithm

Set the heat control method.

[`oFF] Off
[`Pid] PID
[on;of] On-Off

PID

always

[`C;Ag]
[ C.Ag]

Loop
Cool Algorithm

Set the cool control method.

[`oFF] Off
[`Pid] PID
[on;of] On-Off

Off

always

[`C;Cr]
[ C.Cr]

Loop
Cool Output Curve

Select a special cool output curve to
change the responsiveness of the system.

[`oFF] Off
[`Cr;A] Curve A
[`Cr;b] Curve B

Off

Cool Algorithm is set to
Off.

[t;tUn]
[t.tUn]

Loop
TRU-TUNE+

®

Enable

Enable or disable the TRU-TUNE+

®

adaptive tuning feature.

[``no] No
[`YES} Yes

No

Cool Algorithm or Heat

Algorithm is set to PID.

[t;bnd]
[t.bnd]

Loop
TRU-TUNE+

®

Band

Set the range, centered on the set point,
within which TRU-TUNE+

®

will be in ef-

fect. Use this function only if the controller
is unable to adaptive tune automatically.

0 Auto

1 to 100

0

Cool Algorithm or Heat

Algorithm is set to PID
and TRU-TUNE+

®

En-

able is set to Yes.

[`t;gn]
[ t.gn]

Loop
TRU-TUNE+

®

Gain

Select the responsiveness of the TRU-
TUNE+

®

adaptive tuning calculations.

More responsiveness may increase over-
shoot.

1 to 6 Most to least respon-

sive

3

Cool Algorithm or Heat

Algorithm is set to PID
and TRU-TUNE+

®

En-

able is set to Yes.

[t;Agr]
[t.Agr]

Loop
Autotune Aggressiveness

Select the aggressiveness of the autotun-
ing calculations.

[Undr] Under damped
[Crit] Critical damped
[ouer] Over damped

Critical

Cool Algorithm or Heat

Algorithm is set to PID.

[`UFA]
[ UFA]

Loop
User Failure Action

Select what the controller outputs will do
when the user switches control to manual
mode.

[`oFF] Off, sets output power

to 0%

[bPLS] Bumpless, maintains

same output power, if it was
less than 75% and stable,
otherwise 0%

[MAn] Manual Fixed, sets

output power to Manual
Power setting

[USEr] User, sets output

power to last open-loop set
point the user entered

Off

always

Note: Some values will be rounded off to fit in the four-character display. Full values can be read with other interfaces.

If there is only one instance of a menu, no submenus will appear.