Display

Parameter name

Description

Set-

tings

Range

(Integer values for Mod-

bus in parentheses.)

Default

Appears If

[hoUr]
[hoUr]

Step Type Parameters
Hours

Select the hours (plus Minutes and Seconds) for
a timed step.

0 to 99

0

Step Type is set to Time
or Soak.

[Min]
[Min]

Step Type Parameters
Minutes

Select the minutes (plus Hours and Seconds) for
a timed step.

0 to 59

0

Step Type is set to Time
or Soak.

[~SEC]
[ SEC]

Step Type Parameters
Seconds

Select the seconds (plus Hours and Minutes) for
a timed step.

0 to 59

0

Step Type is set to Time
or Soak.

[rate]
[rAtE]

Step Type Parameters
Rate

Select the rate for ramping in degrees or units
per minute.

0 to 9,999.000°F or units

per minute

0 to 5,555.000°C per

minute

0.0

Step Type is set to Rate.

[W;Pi]
[W.Pi]

Step Type Parameters
Wait For Process Instance

Select which analog input Wait For Process will
use.

1 or 2

1

Step Type is set to Wait
For Process and the con-
troller has two process
inputs.

[WPr]
[WPr]

Step Type Parameters
Wait For Process Value

The step will wait until the process value is
equal to the Wait-for Process Value. Once the
Wait For Process is satisfied, this step ends.

-1,999.000 to

9,999.000°F or units

-1,128.000 to

5,537.000°C

0.0°F or

units

-18.0°C

Step Type is set to Wait
For Process.

[WE;1]
[WE.1]
or
[WE;2]
[WE.2]

Step Type Parameters
Wait Event (1 and 2)

Select the event state that must be satisfied
during this step. Digital input 5 provides the
state of Event 1, and digital input 6 provides
the state of Event 2.

[`oFF] Off
[``on] On
[nonE] None

Off

Step Type is set to Wait
Event or Wait for Both.

[~~JS]
[ JS]

Step Type Parameters
Jump Step

Select a step to jump to.

1 to 40

0

Step Type is set to Jump
Loop.

[~~JC]
[ JC]

Step Type Parameters
Jump Count

Set the number of jumps. A value of 0 creates
an infinite loop. Loops can be nested four deep.

0 to 9,999

0

Step Type is set to Jump
Loop.

[~End]
[ End]

Step Type Parameters
End Type
Select what the controller will do when this pro-
file ends.

[`oFF] Control Mode

set to Off

[Hold] Hold last closed-

loop set point in the
profile

[USEr] User, reverts to

previous set point

User

Step Type is set to End.

[Ent1]
[Ent1]
or
[Ent2]
[Ent2]

Step Type Parameters
Event Output (1 and 2)

Select whether Event Output 1 or 2 is on or off
during this step.

[`oFF] Off
[``on] On

Off

Step Type is set to Time,
Rate, Soak, Wait Event,
Wait for Process, Wait
for Both or Jump Loop.

Note: Some values will be rounded off to fit in the four-character display. Full values can be read with another interface.

Advertising