York PREDATOR R-410A User Manual

Page 102

Advertising
background image

528150-YTG-C-1109

102

Johnson Controls Unitary Products

120

(10)

208

16

110

24.9

3.5

6.8

5.5

10.0

None

-

-

-

59.8

65.3

70

80

E18

13.5

2

37.5

67.8

74.7

70

80

E24

18

2

50.0

83.5

90.3

90

100

E36

25.5

2

70.8

109.5

116.4

110

125

E54

40.6

2

112.7

161.9

168.7

175

175

230

16

110

24.9

3.5

6.8

5.5

10.0

None

-

-

-

59.8

65.3

70

80

E18

18

2

45.2

75.1

82

80

90

E24

24

2

60.2

93.2

100

100

100

E36

34

2

85.3

123.2

130.1

125

150

E54

54

2

135.6

150.9

157.8

175

175

460

7.8

52

12.1

1.6

3.4

2.2

5.0

None

-

-

-

29.2

31.4

35

35

E18

18

2

22.6

37.6

40.3

40

45

E24

24

2

30.1

46.6

49.3

50

50

E36

34

2

42.7

61.6

64.4

70

70

E54

54

2

67.8

75.5

78.2

80

90

575

5.7

38.9

8.9

1.3

2.7

1.8

4.0

None

-

-

-

22.1

23.9

25

25

E18

18

2

18.1

30

32.3

30

35

E24

24

2

24.1

37.2

39.5

40

40

E36

34

2

34.1

49.3

51.5

50

60

E54

54

2

54.2

60.3

62.6

70

70

150

(12.5)

208

23.1

160

36

1.5

9.6

5.5

10.0

None

-

-

-

77.6

83.1

100

100

E18

13.5

2

37.5

77.6

83.1

100

100

E24

18

2

50.0

87

93.8

100

100

E36

25.5

2

70.8

113

119.9

125

125

E54

40.6

2

112.7

165.4

172.2

175

175

230

23.1

160

36

1.5

9.6

5.5

10.0

None

-

-

-

77.6

83.1

100

100

E18

18

2

45.2

78.6

85.5

100

100

E24

24

2

60.2

96.7

103.5

100

110

E36

34

2

85.3

126.7

133.6

150

150

E54

54

2

135.6

154.4

161.3

175

175

460

12.2

87

19

0.8

4.8

2.2

5.0

None

-

-

-

40.5

42.7

50

50

E18

18

2

22.6

40.5

42.7

50

50

E24

24

2

30.1

48.3

51.1

50

60

E36

34

2

42.7

63.4

66.1

70

70

E54

54

2

67.8

77.2

80

90

90

575

8.7

62

13.5

0.6

3.9

1.8

4.0

None

-

-

-

29.9

31.7

35

40

E18

18

2

18.1

31.5

33.8

35

40

E24

24

2

24.1

38.7

41

40

45

E36

34

2

34.1

50.8

53

60

60

E54

54

2

54.2

61.8

64.1

70

70

1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.

ZJ078-150 Standard Motor - With Powered Convenience Outlet (Continued)

Size

(Tons)

Volt

Compressors

(each)

OD Fan

Motors

(each)

Supply
Blower

Motor

Pwr
Exh

Motor

Pwr

Conv

Outlet

Electric Heat Option

MCA

1

(Amps)

MCA

1

w/Pwr

Exh

(Amps)

Max Fuse

2

/

Breaker

3

Size

(Amps)

Max Fuse

2

/

Breaker

3

Size w/ Pwr

Exh

(Amps)

RLA

LRA

MCC

FLA

FLA

FLA

FLA

Model

kW

Stages Amps

Advertising