York PREDATOR R-410A User Manual

Page 19

Advertising
background image

528150-YTG-C-1109

Johnson Controls Unitary Products

19

1. 1

st

Stage Capacity is 75% of 2

nd

Stage Capacity.

2. 1

st

Stage Capacity is 70% of 2

nd

Stage Capacity.

3. 2 In. Throwaway, Standard, MERV (Minimum Efficiency Reporting Value) 3.
4. 2 In. Pleated, Optional, MERV 7.
5. 4 In. Pleated, Optional, MERV 14.

CONDENSER FAN DATA

Quantity of fans

1

1

1

Fan diameter (Inch)

24

24

24

Type

Prop

Prop

Prop

Drive type

Direct

Direct

Direct

Quantity of motors

1

1

1

Motor HP each

1/3

1/3

1/3

No. speeds

1

1

1

RPM

850

850

850

Nominal total CFM

3300

3700

3700

BELT DRIVE EVAP FAN DATA

Quantity

1

1

1

Fan Size (Inch)

12 x 9

12 x 9

12 x 9

Type

Centrifugal

Centrifugal

Centrifugal

Motor Sheave

1VM34

1VL44

1VM34

1VL44

1VL40

1VP56

Blower Sheave

AK69

AK69

AK56

AK56

AK61

AK74

Belt

A47

A47

A47

A47

A47

A54

Motor HP each

1-1/2

1-1/2

1-1/2

1-1/2

1-1/2

2

RPM

1725

1725

1725

1725

1725

1725

Frame size

56

56

56

56

56

56

FILTERS

Quantity - Size

4 - (24 x 16 x 2)

3,4

4 - (24 x 16 x 2)

3,4

4 - (24 x 16 x 2)

3,4

4 - (24 x 16 x 4)

5

4 - (24 x 16 x 4)

5

4 - (24 x 16 x 4)

5

ZH037-061 Two Stage Gas Physical Data (Continued)

Component

Models

ZH037

ZH049

ZH061

Nominal Tonnage

3.0

4.0

5.0

Advertising