York PREDATOR R-410A User Manual

Page 71

Advertising
background image

528150-YTG-C-1109

Johnson Controls Unitary Products

71

ZJ078 (6.5 Ton) Bottom Duct

Air Flow

(CFM)

Available External Static Pressure - IWG

1

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
4. Field Supplied Drive.

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

2.0

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

FS

4

Standard 1.5 HP & Drive

Hi Static 2 HP & Drive

1800

603

0.13

656

0.36

718

0.58

784

0.79

851

0.98

914

1.16

968

1.31

1010

1.43

1035

1.53

1039

1.59

2000

627

0.26

680

0.49

742

0.71

808

0.92

875

1.12

937

1.29

992

1.44

1034

1.57

1059

1.66

1063

1.72

2200

650

0.40

703

0.63

765

0.85

831

1.06

898

1.25

961

1.43

1015

1.58

1057

1.71

1082

1.80

1086

1.86

2400

673

0.55

726

0.78

788

1.00

854

1.21

921

1.40

984

1.58

1038

1.73

1080

1.85

1105

1.95

1109

2.01

2600

696

0.71

749

0.94

811

1.16

878

1.37

944

1.56

1007

1.73

1061

1.89

1103

2.01

1128

2.10

1133

2.16

2800

720

0.87

773

1.10

835

1.32

902

1.53

968

1.73

1031

1.90

1085

2.05

1127

2.18

1152

2.27

1157

2.33

3000

745

1.05

798

1.28

860

1.50

926

1.71

993

1.91

1056

2.08

1110

2.23

1152

2.36

1177

2.45

1181

2.51

3200

771

1.24

824

1.47

886

1.69

952

1.90

1019

2.09

1081

2.27

1136

2.42

1178

2.54

1203

2.64

1207

2.70

3400

797

1.44

850

1.67

912

1.89

979

2.10

1045

2.29

1108

2.47

1162

2.62

1204

2.74

1229

2.84

1234

2.90

3 HP & Field Supplied Drive

ZJ090 (7.5 Ton) Bottom Duct

Air Flow

(CFM)

Available External Static Pressure - IWG

1

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
4. Field Supplied Drive.

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

2.0

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

FS

4

Standard 1.5 HP & Drive

Hi Static 3 HP & Drive

2000

644

0.11

698

0.38

755

0.62

814

0.85

874

1.06

933

1.26

990

1.46

1043

1.66

1090

1.87

1131

2.09

2200

666

0.26

720

0.53

777

0.77

836

1.00

896

1.21

956

1.41

1012

1.61

1065

1.81

1113

2.02

1153

2.24

2400

689

0.42

743

0.69

800

0.93

859

1.16

919

1.37

978

1.57

1035

1.77

1088

1.97

1135

2.18

1176

2.40

2600

712

0.60

766

0.87

823

1.11

882

1.34

942

1.55

1002

1.75

1058

1.95

1111

2.15

1159

2.36

1199

2.58

2800

736

0.80

790

1.06

847

1.31

906

1.53

967

1.74

1026

1.94

1082

2.14

1135

2.34

1183

2.55

1223

2.78

3000

761

1.00

815

1.27

872

1.52

931

1.74

991

1.95

1051

2.15

1107

2.35

1160

2.55

1208

2.76

1248

2.98

3200

787

1.22

840

1.49

898

1.74

957

1.96

1017

2.17

1076

2.37

1133

2.57

1186

2.77

1233

2.98

1274

3.20

3400

813

1.46

867

1.73

924

1.97

984

2.19

1044

2.40

1103

2.61

1160

2.80

1212

3.01

1260

3.21

-

-

3600

841

1.70

894

1.97

952

2.21

1011

2.44

1071

2.65

1130

2.85

1187

3.05

-

-

-

-

-

-

3800

869

1.96

923

2.22

980

2.47

1039

2.69

1099

2.90

1158

3.10

1215

3.30

-

-

-

-

-

-

3 HP & Field Supplied Drive

ZJ102 (8.5 Ton) Bottom Duct

Air Flow

(CFM)

Available External Static Pressure - IWG

1

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
4. Field Supplied Drive.

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

2.0

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

FS

4

Standard 2 HP & Drive

Hi Static 3 HP & Drive

2200

685

0.59

739

0.74

791

0.88

841

1.01

889

1.14

936

1.27

981

1.39

1025

1.51

1069

1.63

1111

1.75

2400

702

0.70

756

0.85

808

0.99

858

1.12

906

1.25

953

1.37

999

1.49

1043

1.62

1086

1.74

1129

1.86

2600

722

0.83

776

0.97

828

1.11

878

1.25

926

1.37

973

1.50

1018

1.62

1063

1.74

1106

1.86

1149

1.99

2800

744

0.97

798

1.12

850

1.26

900

1.39

949

1.52

995

1.64

1041

1.76

1085

1.88

1128

2.00

1171

2.13

3000

769

1.13

823

1.28

875

1.42

925

1.55

974

1.68

1020

1.80

1066

1.92

1110

2.05

1153

2.17

1196

2.29

3200

797

1.32

851

1.46

903

1.60

953

1.74

1001

1.86

1048

1.99

1093

2.11

1138

2.23

1181

2.35

1224

2.48

3400

828

1.52

882

1.67

934

1.81

983

1.94

1032

2.07

1078

2.19

1124

2.32

1168

2.44

1212

2.56

1254

2.68

3600

861

1.75

915

1.90

967

2.04

1017

2.17

1065

2.30

1112

2.42

1157

2.54

1201

2.67

1245

2.79

1287

2.91

3800

897

2.00

951

2.15

1002

2.29

1052

2.42

1101

2.55

1147

2.67

1193

2.80

1237

2.92

1280

3.04

1323

3.16

4000

935

2.27

989

2.42

1041

2.56

1091

2.69

1139

2.82

1186

2.95

1231

3.07

1275

3.19

1319

3.31

1362

3.43

4200

976

2.57

1030

2.72

1082

2.86

1132

2.99

1180

3.12

1227

3.24

1272

3.36

-

-

-

-

-

-

3 HP & Field Supplied Drive

Advertising