York PREDATOR R-410A User Manual

Page 42

Advertising
background image

528150-YTG-C-1109

42

Johnson Controls Unitary Products

115°F

125°F

2500

77

118.1

11.1

48.5

41.2

30.6

-

-

-

106.7

12.3

43.2

38.1

27.7

-

-

-

72

110.4

11.1

69.4

58.8

48.3

37.8

-

-

100.8

12.2

65.9

55.6

45.2

34.8

-

-

67

102.7

11.1

90.2

76.5

66.0

55.5

44.9

-

95.0

12.2

88.2

73.0

62.7

52.3

41.9

-

62

93.3

11.1

93.3

93.3

80.0

69.5

59.0

48.5

86.7

12.2

86.7

86.7

78.2

66.5

56.1

45.7

3000

77

120.6

11.2

57.9

45.7

33.6

-

-

-

109.0

12.3

54.4

42.4

30.4

-

-

-

72

112.8

11.1

77.2

65.1

52.9

40.8

-

-

103.0

12.2

73.6

61.6

49.6

37.6

-

-

67

104.9

11.1

96.6

84.5

72.3

60.2

48.0

-

97.0

12.2

92.7

80.8

68.8

56.8

44.8

-

62

95.3

11.1

95.3

95.3

87.7

75.6

63.4

51.3

88.5

12.2

88.5

88.5

84.3

72.3

60.3

48.3

57

97.8

11.0

97.8

97.8

87.5

75.4

63.2

51.1

90.9

12.1

90.9

90.9

81.8

69.8

57.8

45.8

3500

77

123.2

11.2

67.3

50.3

36.5

-

-

-

111.2

12.3

65.5

46.7

33.1

-

-

-

72

115.1

11.2

85.1

71.3

57.6

43.8

-

-

105.1

12.3

81.2

67.6

54.0

40.4

-

-

67

107.1

11.1

103.0

92.4

78.6

64.9

51.1

-

99.0

12.2

97.3

88.5

74.9

61.2

47.6

-

62

97.3

11.1

97.3

97.3

95.4

81.6

67.8

54.1

90.4

12.3

90.4

90.4

90.4

78.1

64.5

50.9

57

99.9

11.0

99.9

99.9

95.2

81.4

67.6

53.9

92.8

12.2

92.8

92.8

89.0

75.4

61.8

48.2

4000

77

125.7

11.2

76.7

54.8

39.5

-

-

-

113.5

12.3

76.6

51.0

35.8

-

-

-

72

117.5

11.2

93.0

77.6

62.2

46.8

-

-

107.3

12.3

88.8

73.6

58.4

43.1

-

-

67

109.3

11.1

109.3

100.4

85.0

69.6

54.2

-

101.0

12.3

101.0

96.2

80.9

65.7

50.5

-

62

99.3

11.1

99.3

99.3

103.1

87.7

72.3

56.9

92.2

12.3

92.2

92.2

92.2

84.0

68.8

53.5

57

101.9

11.1

101.9

101.9

102.8

87.4

72.0

56.7

94.7

12.2

94.7

94.7

94.7

81.1

65.8

50.6

4500

72

118.9

11.2

99.9

83.3

66.6

50.0

-

-

107.9

12.3

95.4

79.0

62.7

46.3

-

-

67

110.6

11.1

110.6

106.1

91.0

74.4

57.8

-

101.7

12.3

101.7

100.9

86.9

70.5

54.2

-

62

100.5

11.1

100.5

100.5

102.3

85.7

69.1

52.4

92.8

12.3

92.8

92.8

92.8

80.0

63.6

47.3

57

103.1

11.1

103.1

103.1

103.6

86.9

70.3

53.7

95.3

12.2

95.3

95.3

95.3

79.7

63.4

47.0

5000

72

120.2

11.2

106.8

89.0

71.1

53.2

-

-

108.6

12.3

101.9

84.4

67.0

49.5

-

-

67

111.9

11.1

111.9

111.9

97.1

79.2

61.4

-

102.3

12.3

102.3

102.3

92.9

75.4

57.9

-

62

101.6

11.1

101.6

101.6

101.6

83.7

65.9

48.0

93.4

12.3

93.4

93.4

93.4

76.0

58.5

41.0

57

104.3

11.1

104.3

104.3

104.3

86.4

68.6

50.7

95.9

12.2

95.9

95.9

95.9

78.4

60.9

43.4

1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower

Performance Table for the kW of the supply air blower motor.

2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

ZH120 (10 Ton) (Continued)

Air on

Evaporator Coil

Temperature of Air on Condenser Coil

Total

Capacity

1

(MBh)

Total
Input

(kW)

2

Sensible Capacity (MBh)

Total

Capacity

1

(MBh)

Total
Input

(kW)

2

Sensible Capacity (MBh)

CFM

WB
(°F)

Return Dry Bulb (°F)

Return Dry Bulb (°F)

90

85

80

75

70

65

90

85

80

75

70

65