York R-410A User Manual

Page 58

Advertising
background image

251933-YTG-J-1009

58

Johnson Controls Unitary Products

048

(4.0)

208-1-60 20.5 115.0

32.0

2.3

7.6

0.0

None

-

-

-

35.5

45

E05

4.0

1

19.2

35.5

45

E07

5.6

1

26.9

43.2

50

E10

8.0

1

38.5

57.6

60

E15

11.9

2

57.2

81.0

90

E20

15.9

2

76.4

105.1

110

230-1-60 20.5 115.0

32.0

2.3

7.6

0.0

None

-

-

-

35.5

45

E05

5.3

1

23.0

37.1

45

E07

7.5

1

32.6

48.6

50

E10

10.6

1

46.1

64.7

70

E15

15.9

2

69.1

92.3

100

E20

21.2

2

92.2

119.9

125

208-3-60 16.0 120.0

25.0

2.3

5.2

0.0

None

-

-

-

27.5

35

E05

4.0

1

11.1

27.5

35

E07

5.6

1

15.5

27.5

35

E10

8.0

1

22.2

34.3

40

E15

11.9

2

33.0

47.8

50

E20

15.9

2

44.1

61.7

70

230-3-60 16.0 120.0

25.0

2.3

5.2

0.0

None

-

-

-

27.5

35

E05

5.3

1

13.3

27.5

35

E07

7.5

1

18.8

29.1

35

E10

10.6

1

26.6

38.4

40

E15

15.9

2

39.9

54.3

60

E20

21.2

2

53.2

70.2

80

460-3-60

7.7

50.0

12.0

1.3

2.6

0.0

None

-

-

-

13.5

20

E07

6.8

1

8.5

13.5

20

E10

10.1

1

12.7

18.4

20

E15

13.6

2

17.1

23.7

25

E20

19.5

2

24.5

32.6

35

575-3-60

6.4

40.0

10.0

1.3

2.0

0.0

None

-

-

-

11.0

15

E10

10.6

1

10.6

15.2

20

E15

15.9

1

16.0

21.6

25

E20

21.2

2

21.3

28.0

30

ZF036-060 (Belt Drive) (Continued)

Size

(Tons)

Volt

Compressors

(each)

OD Fan

Motors

(each)

Supply
Blower

Motor

Pwr

Conv

Outlet

Electric Heat Option

MCA

1

(Amps)

Max

Fuse

2

/

Breaker

3

Size

(Amps)

RLA

LRA

MCC

FLA

FLA

FLA

Model

kW

Stages

Amps

Advertising