York R-410A User Manual

Page 93

Advertising
background image

251933-YTG-J-1009

Johnson Controls Unitary Products

93

060

(5.0)

208-1-60 26.2 134.0

41.0

2.3

7.6

10.0

None

-

-

-

52.7

70

E05

4.0

1

19.2

76.7

90

E07

5.6

1

26.9

86.3

100

E10

8.0

1

38.5

100.7

110

E15

11.9

2

57.2

124.2

125

E20

15.9

2

76.4

148.2

150

E30

22.2

2

106.7

186.1

200

230-1-60 26.2 134.0

41.0

2.3

7.6

10.0

None

-

-

-

52.7

70

E05

5.3

1

23.0

80.3

100

E07

7.5

1

32.6

91.7

110

E10

10.6

1

46.1

107.9

110

E15

15.9

2

69.1

135.5

150

E20

21.2

2

92.2

163.1

175

E30

29.6

2

128.7

206.8

225

208-3-60 15.6 110.0

24.4

2.3

7.6

10.0

None

-

-

-

39.4

50

E05

4.0

1

11.1

53.3

60

E07

5.6

1

15.5

58.8

70

E10

8.0

1

22.2

67.2

70

E15

11.9

2

33.0

80.7

90

E20

15.9

2

44.1

94.6

100

E30

22.2

2

61.6

116.4

125

230-3-60 15.6 110.0

24.4

2.3

7.6

10.0

None

-

-

-

39.4

50

E05

5.3

1

13.3

55.3

60

E07

7.5

1

18.8

62.0

70

E10

10.6

1

26.6

71.3

80

E15

15.9

2

39.9

87.2

90

E20

21.2

2

53.2

103.1

110

E30

29.6

2

74.3

128.4

150

1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.

XP036-060 (Direct Drive) (Continued)

Size

(Tons)

Volt

Compressors

(each)

OD Fan

Motors

(each)

Supply
Blower

Motor

Pwr

Conv

Outlet

Electric Heat Option

MCA

1

(Amps)

Max

Fuse

2

/

Breaker

3

Size

(Amps)

RLA

LRA

MCC

FLA

FLA

FLA

Model

kW

Stages

Amps

Advertising