York R-410A User Manual

Page 77

Advertising
background image

251933-YTG-J-1009

Johnson Controls Unitary Products

77

060

(5.0)

208-1-60 26.2 150.0

41.0

2.3

7.6

10.0

None

-

-

-

52.7

70

E05

4.0

1

19.2

52.7

70

E07

5.6

1

26.9

55.7

70

E10

8.0

1

38.5

70.1

80

E15

11.9

2

57.2

93.5

100

E20

15.9

2

76.4

117.6

125

E30

22.2

2

106.7

155.4

175

230-1-60 26.2 150.0

41.0

2.3

7.6

10.0

None

-

-

-

52.7

70

E05

5.3

1

23.0

52.7

70

E07

7.5

1

32.6

61.1

70

E10

10.6

1

46.1

77.2

80

E15

15.9

2

69.1

104.8

110

E20

21.2

2

92.2

132.4

150

E30

29.6

2

128.7

176.2

200

208-3-60 17.6 120.0

27.5

2.3

5.2

10.0

None

-

-

-

39.5

50

E05

4.0

1

11.1

39.5

50

E07

5.6

1

15.5

39.5

50

E10

8.0

1

22.2

46.8

50

E15

11.9

2

33.0

60.3

70

E20

15.9

2

44.1

74.2

80

E30

22.2

2

61.6

96.0

100

230-3-60 17.6 120.0

27.5

2.3

5.2

10.0

None

-

-

-

39.5

50

E05

5.3

1

13.3

39.5

50

E07

7.5

1

18.8

41.6

50

E10

10.6

1

26.6

50.9

60

E15

15.9

2

39.9

66.8

70

E20

21.2

2

53.2

82.7

90

E30

29.6

2

74.3

108.0

110

460-3-60

8.3

70.0

13.0

1.3

2.6

5.0

None

-

-

-

19.3

25

E07

6.8

1

8.5

19.7

25

E10

10.1

1

12.7

24.7

25

E15

13.6

2

17.1

29.9

30

E20

19.5

2

24.5

38.8

40

E30

28.8

2

36.1

52.8

60

575-3-60

7.4

53.0

11.5

1.3

2.0

4.0

None

-

-

-

16.3

20

E10

10.6

1

10.6

20.2

25

E15

15.9

1

16.0

26.6

30

E20

21.2

2

21.3

33.0

35

E30

30.4

2

30.5

44.1

45

1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.

ZF036-060 (Belt Drive) (Continued)

Size

(Tons)

Volt

Compressors

(each)

OD Fan

Motors

(each)

Supply
Blower

Motor

Pwr

Conv

Outlet

Electric Heat Option

MCA

1

(Amps)

Max Fuse

2

/

Breaker

3

Size

(Amps)

RLA

LRA

MCC

FLA

FLA

FLA

Model

kW

Stages

Amps

Advertising