York R-410A User Manual

Page 87

Advertising
background image

251933-YTG-J-1009

Johnson Controls Unitary Products

87

060

(5.0)

208-1-60 28.8 145.0

45.0

2.3

7.6

10.0

None

-

-

-

55.9

70

E05

4.0

1

19.2

55.9

70

E07

5.6

1

26.9

55.9

70

E10

8.0

1

38.5

70.1

80

E15

11.9

2

57.2

93.5

100

E20

15.9

2

76.4

117.6

125

E30

22.2

2

106.7

155.4

175

230-1-60 28.8 145.0

45.0

2.3

7.6

10.0

None

-

-

-

55.9

70

E05

5.3

1

23.0

55.9

70

E07

7.5

1

32.6

61.1

80

E10

10.6

1

46.1

77.2

80

E15

15.9

2

69.1

104.8

110

E20

21.2

2

92.2

132.4

150

E30

29.6

2

128.7

176.2

200

208-3-60 17.6 123.0

27.5

2.3

7.6

10.0

None

-

-

-

41.9

50

E05

4.0

1

11.1

41.9

50

E07

5.6

1

15.5

41.9

50

E10

8.0

1

22.2

49.8

50

E15

11.9

2

33.0

63.3

70

E20

15.9

2

44.1

77.2

80

E30

22.2

2

61.6

99.0

100

230-3-60 17.6 123.0

27.5

2.3

7.6

10.0

None

-

-

-

41.9

50

E05

5.3

1

13.3

41.9

50

E07

7.5

1

18.8

44.6

50

E10

10.6

1

26.6

53.9

60

E15

15.9

2

39.9

69.8

70

E20

21.2

2

53.2

85.7

90

E30

29.6

2

74.3

111.0

125

1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.

ZR036-060 (Direct Drive) (Continued)

Size

(Tons)

Volt

Compressors

(each)

OD Fan

Motors

(each)

Supply
Blower

Motor

Pwr

Conv

Outlet

Electric Heat Option

MCA

1

(Amps)

Max Fuse

2

/

Breaker

3

Size

(Amps)

RLA

LRA

MCC

FLA

FLA

FLA

Model

kW

Stages

Amps

Advertising